Technical Data - Siemens 13-xx-ST-SBT Series Product Data

Fire detection system
Table of Contents

Advertisement

27
Line card (MS9i) FCL2003-A1

Technical data

27.6
Supply input
Detector line
Mechanical data
Ambient conditions
Standards and approvals
158
Building Technologies
Fire Safety
Technical data
Voltage
Current
Output voltage
Number of integrated line cards
Output current (all outputs together)
Plug-type connection for card cage
Number of devices with 2 loops
Number of devices with 1 loop and 1 stub
Number of devices with 2 stubs
Connectable lines
Protocol
Cable types
Monitored for
Design
Supply output for MS9i devices
Dimensions (L x W x H)
Weight
Operating temperature
Storage temperature
Air humidity
VDS
QA Standards
CE conformity mark
LPCP
DC 20...30 V (Vsys)
Max. 0.75 A
Max. DC 24.9 V
1
Max. 0.5 A
Max. 100
Max. 82
Max. 64
2 loops or
2 stubs or
1 loop and 1 stub
MS9i
All types (recommended: twisted); for
detailed specifications see document
008843
Ground fault
Short-circuit
Open line
Short-circuit-proof
Overvoltage protection (on card cage)
200 mA
160 x 120 x 15 mm
117 g
Min. -5 °C max. +50 °C
Min. -20
max. +60
Max. 93 % rel. air humidity (EN 6006-2)
008837_q_en_--
14.05.2012