Siemens FS20 Commissioning, Maintenance, Troubleshooting

Siemens FS20 Commissioning, Maintenance, Troubleshooting

Fire detection system
Hide thumbs Also See for FS20:
Table of Contents

Advertisement

FS20
Fire detection system
Commissioning
Maintenance
Troubleshooting
MP6
009052_s_en_--
2016-06-02
Building Technologies
Control Products and Systems

Advertisement

Table of Contents
loading

Summary of Contents for Siemens FS20

  • Page 1 FS20 Fire detection system Commissioning Maintenance Troubleshooting Building Technologies 009052_s_en_-- 2016-06-02 Control Products and Systems...
  • Page 2 Issued by: Siemens Switzerland Ltd. Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41 724-2424 www.siemens.com/buildingtechnologies Edition: 2016-06-02 Document ID: 009052_s_en_-- © Siemens Switzerland Ltd, 2006 2 | 188 Building Technologies 009052_s_en_-- Fire Safety 2016-06-02...
  • Page 3: Table Of Contents

    Table of contents About this document ................9 Applicable documents ................11 Download center ..................11 Technical terms and abbreviations .............12 Revision history ..................12 Safety ....................16 Safety instructions ..................16 Safety regulations for the method of operation ...........18 Standards and directives complied with............20 2.3.1 CPR conformity and firmware version .........20 Release Notes ...................20...
  • Page 4 B1 - Commissioning standalone 'Station' with PC, without pre-configuration ..............41 B2 - Commissioning standalone 'Station' with PC, with pre-configuration ...42 C- Commissioning networked 'Stations' ..........43 Commissioning FC2080 ...............44 Commissioning FG2020...............45 Adding a 'Station' to an existing 'Site' .............46 Merging two 'Sites' ................47 13.1 Adding 'Site' B to 'Site' A ................
  • Page 5 Commissioning of control panel with AnalogPLUS detector line ....64 Changing and expanding the AnalogPLUS detector line ......65 18.1 Adding a device to the detector line ............65 18.2 Replacing a device with one of a different type ...........65 18.3 Removing a device permanently ..............66 18.4 Replacing a non-stationary device of the same type ........66 18.5 Replacing multiple non-stationary devices of the same type with a line restart..................66...
  • Page 6 21.16 Delete the device on Person Machine Interface ......... 86 21.17 Remove the elements ................86 21.18 Testing detectors ..................87 21.18.1 Activate the detector ..............87 21.18.2 Testing logged test activations ............ 87 21.19 Using a detector exchanger and tester or an intelligent detector tester ..88 21.20 Switching on test mode ................
  • Page 7 Updating the firmware ............... 117 29.1 Preparation and security ................117 29.2 Station: Updating the FW of the main CPU and additional CPUs ....118 29.2.1 Standalone station and SAFEDLINK station ......118 29.2.2 Router station and Ethernet station ...........119 29.2.3 Modular station with CPU card ..........120 29.2.4 Updating several 'Stations' simultaneously ........121 29.2.5...
  • Page 8 Repair ..................... 165 31.1 Disconnect the station from the power supply .......... 165 31.2 Spare parts ....................166 31.3 Fault messages on the Person Machine Interface ........166 31.4 Fault indicators on components ............... 168 31.5 Communication problems in networked systems ........169 31.6 Correcting swapped devices ..............
  • Page 9: About This Document

    Goal and purpose This document provides information and work steps for installing, commissioning, maintaining and repairing the fire detection system FS20. More information can be found in the corresponding documents under 'Applicable documents'. To understand this document, you must have complete knowledge of document 008836.
  • Page 10 About this document Applicable documents Date format The date format in the document corresponds to the recommendation of international standard ISO 8601 (format YYYY-MM-DD). Conventions for text marking Markups Special markups are shown in this document as follows: ⊳ Requirement for a behavior instruction Behavior instruction with at least two operation sequences –...
  • Page 11: Applicable Documents

    FS20 Fire Detection System, Configuration 009310 FT2010 Floor Repeater Terminal, Operation 009311 FT2011 Floor Repeater Display, Operation 009690 FS20 Fire Detection System, Components / Spare Parts / Repair Parts 009718 FDUD293 Intelligent Detector Tester, Operation 009854 FDUZ221 MCL-USB adapter, Mounting...
  • Page 12: Technical Terms And Abbreviations

    About this document Technical terms and abbreviations 1.3 Technical terms and abbreviations Term Explanation Base data variant Product version FDnet Addressed detector line Firmware Maintenance and commissioning link 'MCP' Abbreviation for 'Manual call point' You will find details of further technical terms and abbreviations in the 'Glossary' chapter.
  • Page 13 About this document Revision history Version Edition date Brief description Revised: Chapter structure Referenced documents updated Disconnecting 'Station' from the power supply Merging two 'Sites' Loading data to the 'Station' Loading configuration from the PC to the 'Station' Loading configuration from the 'Station' to the PC Creating a backup of the 'Site' configuration Preparing 'Station' for commissioning –without BDV installation Loading automatically created configuration to the PC...
  • Page 14 About this document Revision history Version Edition date Brief description Revised: Firmware update updated Replacing a device without SintesoWorks Chapters 'Removing or replacing non-stationary devices' and 'Changing and expanding the detector line' have been combined into one new chapter called 'Changing and expanding the FDnet/C-NET detector line' Firmware update FDCW241 CPR replaces CPD: The Construction Products Regulation (CPR 305/2011)
  • Page 15 About this document Revision history Version Edition date Brief description 10.2009 Chapter 15 and 16: Commissioning steps revised 04.2009 Modifications for MP2.1 02.2009 "Commissioning control panel with collective lines" chapter revised Chapter: "Updating the firmware of the peripheral devices (FT2010, FT2011, FDCW221)"...
  • Page 16: Safety

    Safety Safety instructions 2 Safety 2.1 Safety instructions The safety notices must be observed in order to protect people and property. The safety notices in this document contain the following elements: ● Symbol for danger ● Signal word ● Nature and origin of the danger ●...
  • Page 17 Safety Safety instructions How risk of injury is presented Information about the risk of injury is shown as follows: WARNING Nature and origin of the danger Consequences if the danger occurs ● Measures / prohibitions for danger avoidance How possible damage to property is presented Information about possible damage to property is shown as follows: NOTICE Nature and origin of the danger...
  • Page 18: Safety Regulations For The Method Of Operation

    2.2 Safety regulations for the method of operation National standards, regulations and legislation Siemens products are developed and produced in compliance with the relevant European and international safety standards. Should additional national or local safety standards or legislation concerning the planning, mounting, installation,...
  • Page 19 Disregard of the safety regulations Before they are delivered, Siemens products are tested to ensure they function correctly when used properly. Siemens disclaims all liability for damage or injuries caused by the incorrect application of the instructions or the disregard of danger warnings contained in the documentation.
  • Page 20: Standards And Directives Complied With

    Safety Standards and directives complied with 2.3 Standards and directives complied with A list of the standards and directives complied with is available from your Siemens contact. 2.3.1 CPR conformity and firmware version In order to satisfy Ordinance No. 305/2011 (the Construction Products Regulation –...
  • Page 21: Cyber Security Disclaimer

    Safety Cyber security disclaimer 2.5 Cyber security disclaimer Products, solutions and services from Siemens include security functions to ensure the secure operation of building automation and control, fire safety, security management, and physical security systems. The security functions on these products, solutions and services are important components of a comprehensive security concept.
  • Page 22: Mounting / Installation

    Mounting / Installation Installing and checking the detector line 3 Mounting / Installation 3.1 Installing and checking the detector line You will find details on the technical term ↑ 'FDnet' in the chapter 'Glossary'. Most FDnet devices are installed on a base and can be changed with ease. The bases of non-stationary FDnet devices and stationary FDnet devices must be installed and uninstalled when the FDnet detector line is switched off and disconnected from the power supply.
  • Page 23: Checking The Detector Line

    Mounting / Installation Mount and install 'Station' 3.1.3 Checking the detector line NOTICE Simultaneous connection of line tester and FDnet detector line to the control panel Damage to line tester or control panel ● Do not connect the line tester and the FDnet detector line to the control panel at the same time.
  • Page 24: Connectivity And Communication With 'Station

    The Windows firewall may prevent the PC connecting to the ↑ 'Station'. ● A functioning Ethernet connection between the SintesoWorks on the PC and the FS20 control panels is required to update the firmware, for example. Setting Windows firewall ●...
  • Page 25: Windows 7 / Windows 8 / Windows 10

    Setting Windows firewall 4.1.2 Windows 7 / Windows 8 / Windows 10 There are different ways of setting up firewall rules in Windows 7/8/10. The following settings apply for Siemens PCs which use group guidelines controlled by the domain. NOTICE The following settings must be made under Local Security Policy.
  • Page 26: Network Parameters

     The new firewall rule is now configured. NOTICE Security vulnerability in operating system due to open ports Unauthorized access to your PC ● Deactivate the firewall rule configured above after the firmware update. 4.2 Network parameters Ports in FS20 Port number Transport Application Comment protocol protocol...
  • Page 27: Connecting The Pc To The Station

    Connectivity and communication with 'Station' Connecting the PC to the station 4.3 Connecting the PC to the station For most commissioning, maintenance and repair work a PC with installed SintesoWorks is required. The figure below shows the connection between the PC and ↑...
  • Page 28: Loading Data To The 'Station

    Connectivity and communication with 'Station' Loading data to the 'Station' 4.5 Loading data to the 'Station' Data is loaded from SintesoWorks to the 'Station' when the following commands are performed. ● 'Initialize station' ● 'Download site' If you use a number of network cards on the PC, observe the information in the chapter 'IP settings for several network cards' in document 009078.
  • Page 29 Connectivity and communication with 'Station' Initializing 'Station' Initialize 'Station' NOTICE Connection module (card cage) FCA2006-A1 defective or installed incorrectly Control panels identified incorrectly, e.g. FC2060 identified as FC2040. ● Check that the connection module (card cage) FCA2006-A1 is installed correctly. NOTICE Faulty initialization for networked station During initialization, the station must not be connected to the network or any other...
  • Page 30: Loading Configuration From The Pc To The Station

    WARNING Activation of fire or smoke dampers If fire or smoke dampers are connected to the FS20 via an input/output module, they may be activated when the station is switched off or when the station or detector line is restarted.
  • Page 31 Connectivity and communication with 'Station' Loading configuration from the PC to the station ϖ The ↑ 'Site' is opened in SintesoWorks. ϖ The PC is connected to the 'Station'. ϖ Networked 'Stations' are initialized. ϖ 'Station' and SintesoWorks have the same 'Site' ID. ϖ...
  • Page 32: Loading Configuration From The Station To The Pc

    Connectivity and communication with 'Station' Loading configuration from the station to the PC 4.8 Loading configuration from the station to the PC The 'Upload site' function can be used to load the configuration of a ↑ 'Site' to SintesoWorks on the PC. ϖ...
  • Page 33  The progress is displayed in the 'Create backup embedded configuration' window. Backup file ● The backup file is saved in the following directory as standard: C:\ProgramData\Siemens\FX2030\[Softwareversion]\Sites\embeddedBackups ● The backup file has the following name: <'Site' name>_<backup counter>(_incomplete).fsc Example: Test_Site_007_incomplete.fsc –...
  • Page 34: Commissioning Overview

    Commissioning overview Commissioning variants 5 Commissioning overview The ↑ 'Stations' on the FCnet, such as control panels FC2020/FC2040 and fire terminals FT2040 and FT2080, are connected to the power supply and commissioned by the installation and commissioning personnel. ● Networked 'Stations' must only be commissioned with SintesoWorks. ●...
  • Page 35: Definition Of Terms

    Commissioning overview Definition of terms 5.2 Definition of terms ↑ Auto-configuration Auto-configuration is performed using a command on the ↑ Person Machine Interface. In this process, the FDnet devices are read in and a configuration created. There are two types of auto-configuration. ●...
  • Page 36: Standard Gateway

    Commissioning overview Standard gateway 5.3 Standard gateway The standard gateway address of the ↑ station is pre-configured as 192.168.200.254. When using a router, an address does not need to be set at the station. Following startup, the station automatically connects to the router. A tool is not required to establish a remote connection.
  • Page 37: License

    Commissioning overview License Fire terminal (Touch) FT2080 Buttons Description Opens the main menu Opens the topology Navigation buttons for changing to a higher or lower level in the hierarchy Opens the 'Select command' dialog window Command execution OK Command execution not OK ●...
  • Page 38: Commissioning Standalone 'Station' Without Pc

    A - Commissioning standalone 'Station' without PC License 6 A - Commissioning standalone 'Station' without PC The procedure in this chapter is only valid for ↑ standalone 'Stations'. In this commissioning variant, a ↑ 'Station' without a PC and a SintesoWorks are commissioned.
  • Page 39: Configuring The Power Supply

    A - Commissioning standalone 'Station' without PC Configuring the power supply 6.1 Configuring the power supply If the ↑ 'Station' is equipped with a power supply and batteries, the power supply does not have to be configured. In all other cases the power supply must be configured.
  • Page 40: Setting Detector Parameter Sets

    A - Commissioning standalone 'Station' without PC Setting detector parameter sets 6.3 Setting detector parameter sets 1. Select 'Topology' > ↑ 'Detection tree' > 'Area' > ↑ 'Section' > 'Zone' > 'Detect.' in the main menu. 2. Press the 'MoreOptions' softkey. 3.
  • Page 41: B1 - Commissioning Standalone 'Station' With Pc, Without Pre-Configuration

    B1 - Commissioning standalone 'Station' with PC, without pre-configuration 7 B1 - Commissioning standalone 'Station' with PC, without pre-configuration First auto-configure the ↑ 'Station' in this commissioning variant. Then adapt the auto-configuration manually in SintesoWorks. The procedure in this chapter applies exclusively to ↑ standalone 'Stations' and is only valid for FDnet detector lines.
  • Page 42: B2 - Commissioning Standalone 'Station' With Pc, With Pre-Configuration

    B2 - Commissioning standalone 'Station' with PC, with pre-configuration 8 B2 - Commissioning standalone 'Station' with PC, with pre-configuration The procedure in this chapter is only valid for FDnet detector lines. In this commissioning variant, in SintesoWorks, first manually configure a ↑ 'Site' up to 'Line' level.
  • Page 43: Commissioning Networked 'Stations

    C- Commissioning networked 'Stations' 9 C- Commissioning networked 'Stations' You will find information on converting a ↑ standalone 'Station' to a networked ↑ 'Station' in chapter 'Converting a standalone station to a networked station [➙ 81]'. Prerequisites ● The ↑ detector lines and FDnet devices are installed. ●...
  • Page 44: Commissioning Fc2080

    Commissioning FC2080 10 Commissioning FC2080 Because of the fact that the FC2080 fire control panel has no integrated operating unit, you must configure at least one operating unit within the 'Site' in such a way that it has a ↑ visibility of the FC2080. Commissioning 1.
  • Page 45: Commissioning Fg2020

    Commissioning FG2020 11 Commissioning FG2020 Because of the fact that the FG2020 has no integrated operating unit, you must configure at least one operating unit within the 'Site' in such a way that it has a ↑ visibility of the FG2020. Commissioning 1.
  • Page 46: Adding A 'Station' To An Existing 'Site

    Adding a 'Station' to an existing 'Site' 12 Adding a 'Station' to an existing 'Site' Prerequisites ● The ↑ detector lines and FDnet devices are installed. ● The acceptance test has been carried out for the detector lines. ● The ↑ 'Station' is installed, but the batteries are not connected yet. ●...
  • Page 47: Merging Two 'Sites

    Merging two 'Sites' Setting detector parameter sets 13 Merging two 'Sites' You can merge two ↑ 'Sites' to form one 'Site'. NOTICE Merging standalone 'Stations' You have to convert standalone 'Stations' to networked ↑ 'Stations' to combine 'Stations' into one ↑ 'Site'. You will find more information in chapter 'Converting a standalone station to a networked station [➙...
  • Page 48: Adding 'Site' B To 'Site' A

    Merging two 'Sites' Adding 'Site' B to 'Site' A 13.1 Adding 'Site' B to 'Site' A ϖ ↑ 'Site' A is open in SintesoWorks. 1. Select 'Edit' > 'Merge sites'.  The 'Merge sites' wizard opens. 2. Enter the path and name of 'Site' B that you would like to merge with 'Site' A. 3.
  • Page 49: Changing And Expanding The Fdnet/C-Net Detector Line

    Changing and expanding the FDnet/C-NET detector line Extending the detector line to include additional devices 14 Changing and expanding the FDnet/C-NET detector line 14.1 Extending the detector line to include additional devices NOTICE Incorrect assignment between detector/detector zone and customer text Inaccurate messages in the event of an alarm ●...
  • Page 50: Configure A New Device

    Changing and expanding the FDnet/C-NET detector line Replacing stationary devices of the same type 14.1.2 Configure a new device 1. Extend the configuration in SintesoWorks, e.g., in the ↑ 'Detection tree'. 2. Allocate the read-in devices to the elements of the detection tree or the control tree in SintesoWorks.
  • Page 51: Permanently Removing Stationary Devices

    Changing and expanding the FDnet/C-NET detector line Permanently removing stationary devices 14.3 Permanently removing stationary devices You will find additional information about the individual steps on the specified pages. 1. Switch the FDnet detector line off. Link [➙ 82] 2. Remove the FDnet devices. Link [➙ 85] 3.
  • Page 52: Temporarily Removing Multiple Non-Stationary Devices

    Changing and expanding the FDnet/C-NET detector line Removing or replacing non-stationary devices 14.4.2 Temporarily removing multiple non-stationary devices For the purpose of painting work, it may be necessary to temporarily remove the FDnet devices in a room. Each FDnet device must then be re-inserted in its original base.
  • Page 53: Replacing Non-Stationary Devices Of The Same Type

    Changing and expanding the FDnet/C-NET detector line Removing or replacing non-stationary devices 14.4.4 Replacing non-stationary devices of the same type You will find additional information about the individual steps on the specified pages. 1. Switch the test mode on. Link [➙ 89] 2.
  • Page 54: Replacing 'Manual Call Point' Of The Same Type

    Changing and expanding the FDnet/C-NET detector line Replacing 'Manual call point' of the same type 14.4.5.1 Replacing a device in the 'Zone' 1. Select the 'Zone' in which you have replaced a device in SintesoWorks. The 'Find' or 'Find and replace' functions can be used to do this. 2.
  • Page 55: Switching On The Replace Mode

    Changing and expanding the FDnet/C-NET detector line Replacing 'Manual call point' of the same type 14.5.1 Switching on the replace mode 1. Select 'Functions' > 'All functions' > 'Detector' in the main menu. 2. In the 'Zone', enter the 'Zone' address and press <ok>. 3.
  • Page 56: Convert Two Stubs Into A Loop

    Changing and expanding the FDnet/C-NET detector line Convert two stubs into a loop 14.6 Convert two stubs into a loop You will find additional information about the individual steps on the specified pages. ϖ The two ↑ stubs are assigned to the same line pair, e.g., 'Line' 11 and 'Line' 12. 1.
  • Page 57: Commissioning The Control Panel With Ms9I Detector Lines

    Commissioning the control panel with MS9i detector lines 15 Commissioning the control panel with MS9i detector lines Prerequisites ● The ↑ 'Station' is installed, but the batteries are not connected yet. ● The cables for the ↑ detector lines and the mains supply have been inserted in the 'Station', but not yet connected.
  • Page 58: Commissioning Control Panel With Collective Detector Lines

    Commissioning control panel with collective detector lines Pre-configuration 16 Commissioning control panel with collective detector lines Prerequisites ● The ↑ 'Station' is installed, but the batteries are not connected yet. ● The cables for the ↑ detector lines and the mains supply have been inserted in the 'Station', but not yet connected.
  • Page 59: Reference Measurement With Eol 4K7 And 3K3

    Commissioning control panel with collective detector lines Reference measurement with EOL 4k7 and 3k3 16.2 Reference measurement with EOL 4k7 and 3k3 A reference measurement is performed each time a ↑ collective detector line is started up if the end-of-line element (EOL) 4k7 or 3k3 is used. If the cause of a fault, e.g.
  • Page 60: Line Fault' Error Message

    Commissioning control panel with collective detector lines Troubleshooting procedure 16.3.1 'Line Fault' error message If the error message 'Line fault' is displayed for collective detector lines once the ↑ 'Station' has started, the cause may be a change in line resistance. ●...
  • Page 61: Checking Line Resistance

    Commissioning control panel with collective detector lines Troubleshooting procedure 16.4.2 Checking line resistance To check the line resistance, a universal measuring instrument with internal resistance of >20 kΩ/V, a voltage range of 15 V to 30 V, and a resistance range of 10 kΩ...
  • Page 62: Measuring Insulation Values

    Commissioning control panel with collective detector lines Troubleshooting procedure 16.4.4 Measuring insulation values 1. Switch the ↑ collective detector line off: – Switch off the 'Zone' that is assigned to the collective detector line. The 'Zone' and the physical collective detector line are then switched off at the same time.
  • Page 63: Commissioning The Collective Detector Line Step-By-Step

    Commissioning control panel with collective detector lines Troubleshooting procedure 16.4.5 Commissioning the collective detector line step-by-step A 'Detector' with KMK = 1 increases the line current by approx. 0.1 mA. 1. Connect the universal measuring instrument to the start of the ↑ collective detector line.
  • Page 64: Commissioning Of Control Panel With Analogplus Detector Line

    You need a pre-configuration in order to commission an AnalogPLUS detector line. If you are using the ↑ line card (AnalogPLUS) for AlgoRex data migration, you must migrate the AlgoRex configuration data for the FS20 fire detection system. You will find more information about AlgoRex data migration in document 009078.
  • Page 65: Changing And Expanding The Analogplus Detector Line

    Changing and expanding the AnalogPLUS detector line Adding a device to the detector line 18 Changing and expanding the AnalogPLUS detector line 18.1 Adding a device to the detector line NOTICE Unable to detect device when it is read in An AnalogPLUS detector line cannot be expanded by reading a device in on the ↑...
  • Page 66: Removing A Device Permanently

    Changing and expanding the AnalogPLUS detector line Removing a device permanently 18.3 Removing a device permanently To remove a device from the AnalogPLUS detector line for good, follow the steps below: 1. Load the configuration from the ↑ 'Station' to the PC. Link [➙ 32] 2.
  • Page 67: Replacing Stationary Devices Of The Same Type

    Changing and expanding the AnalogPLUS detector line Replacing stationary devices of the same type 18.6 Replacing stationary devices of the same type To replace ↑ stationary devices of the same type on the AnalogPLUS detector line, follow the steps below: ϖ...
  • Page 68: Readdressing Devices

    Changing and expanding the AnalogPLUS detector line Readdressing devices 18.9 Readdressing devices To readdress devices on the AnalogPLUS detector line, follow the steps below: ϖ You have already commissioned the AnalogPLUS detector line. ϖ The line is in ↑ normal operation. 1.
  • Page 69: Commissioning Of Control Panel With Interactive Detector Line

    Commissioning of control panel with interactive detector line Replacing an AnalogPLUS device 19 Commissioning of control panel with interactive detector line The commissioning steps in this chapter apply for ↑ detector lines with ↑ line card (interactive) and line card (interactive, Ex). You will find information about commissioning an interactive detector line and about AlgoRex data migration in chapter 'Commissioning of interactive detector line for AlgoRex data migration [➙...
  • Page 70: Commissioning Of Interactive Detector Line For Algorex Data Migration

    If you are using the ↑ line card (interactive) for AlgoRex data migration, you must create a pre-configuration. To do this, migrate the AlgoRex configuration data for the FS20 fire detection system. You will find more information about AlgoRex data migration in document 009078. See chapter 'Applicable documents'.
  • Page 71: Changing And Expanding The Interactive Detector Line

    Changing and expanding the interactive detector line Adding a device to the detector line 20 Changing and expanding the interactive detector line 20.1 Adding a device to the detector line WARNING No alarm when there is no logical ↑ assignment If a device is read in on the ↑...
  • Page 72: Removing A Device Permanently

    Changing and expanding the interactive detector line Removing a device permanently 20.3 Removing a device permanently To remove a device from the interactive detector line for good, follow the steps below: ϖ You have already commissioned the interactive detector line. ϖ...
  • Page 73: Replacing Stationary Devices Of The Same Type

    Changing and expanding the interactive detector line Replacing stationary devices of the same type 20.5 Replacing stationary devices of the same type To replace stationary devices of the same type on the interactive detector line, follow the steps below: ϖ You have already commissioned the interactive detector line. ϖ...
  • Page 74: Converting A Stub Or Loop

    Changing and expanding the interactive detector line Converting a stub or loop 20.7 Converting a stub or loop The following conversion options are available for the interactive detector line: ● Converting a ↑ stub into a ↑ loop ● Converting a loop into a stub To convert an interactive detector line, follow the steps below: 1.
  • Page 75: Locating Wire Breaks

    Changing and expanding the interactive detector line Locating wire breaks 20.9 Locating wire breaks For the purpose of locating a wire break in a ↑ loop, the ↑ detector line can be supplied via just the forward connection or the backward connection. If the ↑...
  • Page 76: Detailed Commissioning Steps

    Detailed commissioning steps Preparing 'Station' for commissioning 21 Detailed commissioning steps In the following chapters, you will find detailed commissioning steps that are referred to in several chapters. 21.1 Preparing 'Station' for commissioning 1. Connect the cables for the ↑ detector lines and the peripheral devices. 2.
  • Page 77: Preparing 'Station' For Commissioning -Without Bdv Installation

    Detailed commissioning steps Preparing 'Station' for commissioning –without BDV installation 21.2 Preparing 'Station' for commissioning –without BDV installation 1. Connect the cables for the ↑ detector lines and the peripheral devices. 2. Connect the power supply (mains and batteries).  The ↑ 'Station' starts and reads in the internal hardware. ...
  • Page 78: One-Step Commissioning

    – Check whether the memory cards inside your device can be encrypted. You will find the Siemens CERT Security Measure Plan for Android Devices at https://www.cert.siemens.com/rules/mobile/. Assignable elements You can only assign manual and automatic channels of the type 'Sensor' with 'Sinteso Test'.
  • Page 79: Auto-Configuring 'Station

    Detailed commissioning steps Auto-configuring 'Station' 21.4 Auto-configuring 'Station' 1. Select 'Topology' > 'Hardware tree' > ↑ 'Station' in the main menu. 2. Press the 'More Options' softkey and select 'Execute commands'. 3. Select the 'Auto-configure station' command.  The 'Station' is auto-configured. ...
  • Page 80: Loading Automatically Created Configuration To The Pc

    Detailed commissioning steps Loading automatically created configuration to the PC 21.6 Loading automatically created configuration to the The description in this chapter only applies if a configuration has not yet been loaded to the 'Station' and if the ↑ BDV was installed at the 'Station' after the 'Station' was started for the first time.
  • Page 81: Converting A Standalone Station To A Networked Station

    ϖ The configuration for an ↑ 'Site' with a standalone 'Station' is loaded to SintesoWorks. 1. Select the 'Network' task card. 2. Open 'Global system configuration' > 'FS20 network configuration' > 'Ethernet sub-net' in the tree view. 3. Select 'Connections' to configure an Ethernet network.
  • Page 82: Switch Off

    Detailed commissioning steps Switch off 21.9 Switch off 21.9.1 Safety during switch-off WARNING System parts that have been switched off make it impossible to acquire and process alarms or faults! Fire may spread unhindered. ● Deploy staff to monitor the deactivated area. ●...
  • Page 83: Switching On

    WARNING Activation of fire or smoke dampers If fire or smoke dampers are connected to the FS20 via an input/output module, they may be activated when the station is switched off or when the station or detector line is restarted.
  • Page 84: Freezing Outputs

    Detailed commissioning steps Freezing outputs 21.12 Freezing outputs You can freeze outputs with connected fire dampers to prevent them from being activated if the 'Station' or line is restarted or in the event of a module reset. A restart is required if a modified configuration is loaded to the 'Station'. Duration of freeze The output freeze lasts until the next restart or module reset.
  • Page 85: Read In Devices On Detector Line

    Detailed commissioning steps Read in devices on detector line 21.14 Read in devices on detector line NOTICE Incorrect order for reading in a ↑ loop Error when reading in a loop. The FDnet detector lines are detected as ↑ stubs during the first system startup, e.g., 'Line' 11, 'Line' 12 (2-digit line number), even if they are connected as a loop.
  • Page 86: Delete The Device On Person Machine Interface

    Detailed commissioning steps Delete the device on Person Machine Interface 21.16 Delete the device on Person Machine Interface 1. Mark the corresponding device fault message. 2. Press the 'More Options' softkey. 3. Select the 'Show topology' menu item.  The logical channel is displayed. For some devices, 'Device' is displayed directly.
  • Page 87: Testing Detectors

    Detailed commissioning steps Testing detectors 21.18 Testing detectors The commissioning personnel perform the function test for the ↑ automatic fire detectors and the 'Manual call points'. You will find additional information about the individual steps on the specified pages. ϖ The ↑ detector line has been commissioned. 1.
  • Page 88: Using A Detector Exchanger And Tester Or An Intelligent Detector Tester

    Detailed commissioning steps Using a detector exchanger and tester or an intelligent detector tester 21.19 Using a detector exchanger and tester or an intelligent detector tester In this chapter, 'service device' refers to the following devices: ● Detector exchanger and tester FDUD292 ●...
  • Page 89: Switching On Test Mode

    Detailed commissioning steps Switching on test mode 21.20 Switching on test mode 1. Select 'Topology' > ↑ 'Detection tree' in the main menu. 2. Select the element you want to switch to test mode: 'Area', 'Section', or 'Zone' 3. Press the 'More Options' softkey and select 'Execute commands'. 4.
  • Page 90: Switch On Normal Operation

    Detailed commissioning steps Switch on normal operation 21.21 Switch on normal operation There is a shortened procedure for switching individual 'Zones' to ↑ normal operation. The procedure is described in the following section: 'Switching 'Zone' to normal operation' Switching 'Area', 'Section' or 'Zone' to ↑ normal operation 1.
  • Page 91: Rectify Localization Errors

    Detailed commissioning steps Rectify localization errors 21.22 Rectify localization errors 1. Use 'Topology' > 'Hardware tree' > ↑ 'Station' > ↑ Line card > Detector line to select the corresponding ↑ detector line in the main menu. 2. Press the 'MoreOptions' softkey and select 'Execute commands'. 3.
  • Page 92: Commissioning Ethernet Switch (Mm) Fn2008-A1

    This description focuses on correctly integrating the 'Ethernet switch (MM) FN2008-A1' in the fire detection installation. More information about the product can be found on the data carrier in the scope of supply and at the following address: http://support.automation.siemens.com (Manufacturer designation: Scalance X204-2) NOTICE...
  • Page 93: Assign Ip Address

    Commissioning Ethernet switch (MM) FN2008-A1 Assign IP address 22.2 Assign IP address The FN2008-A1 is displayed as X204-2 in Primary Setup Tool. ϖ Primary Setup Tool is installed on the PC. ϖ Several FN2008-A1 are physically linked in the system. 1.
  • Page 94: Configuring Fn2008-A1 Using Internet Browser

    Commissioning Ethernet switch (MM) FN2008-A1 Configuring FN2008-A1 using Internet browser 22.3 Configuring FN2008-A1 using Internet browser A configuration is available via the localization manager. We recommend using the configuration and if necessary making system-specific adaptations. NOTICE Incorrect settings of the ports Malfunction ●...
  • Page 95: Commissioning Security Module (Firewall) Fn2009-A1

    (firewall) FN2009-A1' in the fire detection installation. More information about the product can be found on the data carrier in the scope of supply and at the following address: http://support.automation.siemens.com (Manufacturer designation: Scalance S612) A configuration is available via the localization manager. We recommend using the configuration and if necessary making system-specific adaptations.
  • Page 96: Installing Security Configuration Tool

    Commissioning security module (firewall) FN2009-A1 Installing Security Configuration Tool 23.1 Installing Security Configuration Tool The 'Security Configuration Tool' software is included in the scope of supply for the FN2009-A1. Install the 'Security Configuration Tool' software. κ  The software is installed in the standard path 'SIMATIC' > 'SCALANCE' > 'Security' >...
  • Page 97: Selecting Type And Entering Mac Address

    Commissioning security module (firewall) FN2009-A1 Selecting type and entering MAC address 23.2 Selecting type and entering MAC address The corresponding MAC address can be found on the front of the FN2009-A1. The FN2009-A1 is type S612V2. Preparation ϖ The PC is connected to FN2009-A1. ϖ...
  • Page 98: Entering Network Settings

    Commissioning security module (firewall) FN2009-A1 Entering network settings 23.3 Entering network settings ϖ The network topology is known. ϖ 'Advanced Mode' is selected. Enter the network settings in the following order: κ – External IP address 'IP Address ext.' – Routing mode 'Routing Mode' –...
  • Page 99 Commissioning security module (firewall) FN2009-A1 Entering network settings 2. Select the 'Routing Mode' tab.  The following entry mask is displayed: 3. Check the 'Routing active' checkbox. 4. Enter the following 'internal module IP address': 192.168.201.2. 5. Confirm input with 'OK'. ...
  • Page 100: Creating Ip Service Definitions

    Commissioning security module (firewall) FN2009-A1 Creating IP service definitions Loading the network settings to FN2009-A1 ϖ MAC address is entered. ϖ IP addresses are entered. 1. Highlight the FN2009-A1 module in the project. 2. Select the 'Transfer > 'To Module' menu. ...
  • Page 101: Creating Firewall Rules

    Commissioning security module (firewall) FN2009-A1 Creating firewall rules 7. Enter the two optional ICMP services required as shown in the figure below: – 'Name': ICMP0, 'Type': Echo Request, 'Code': No code – 'Name': ICMP1, 'Type': Echo Reply, 'Code': No code ...
  • Page 102 Commissioning security module (firewall) FN2009-A1 Creating firewall rules 3. Select the 'Firewall Settings' tab.  The following window is displayed without entries: 4. Click on 'Add Rule' for each firewall rule you would like to create. 5. Select the corresponding settings and IP services from the dropdown list fields. 6.
  • Page 103: Commissioning Ethernet Switch (Modular) Fn2012-A1

    Commissioning Ethernet switch (modular) FN2012-A1 Standalone FN2012-A1 24 Commissioning Ethernet switch (modular) FN2012-A1 Malfunctions during a partial upgrade Ethernet switch (modular) FN2012 is not compatible with Ethernet switch (MM) FN2008 and so may only be used in panels ≥MP6. See also 1 Updating the FW of Ethernet switch (modular) FN2012-A1 [➙...
  • Page 104: Specifying A Pre-Configured Ip Address

    Commissioning Ethernet switch (modular) FN2012-A1 Standalone FN2012-A1 24.1.1 Specifying a pre-configured IP address You must assign a pre-configured IP address to a standalone FN2012-A1 as part of its commissioning process. 1. Use the rotary switch on the FN2012-A1 to select an IP address in accordance with the table further below.
  • Page 105: Fn2012-A1 Integrated Into Station

    2. Configure an IP address for the FN2012-A1 that is valid on the sub-net: – In Engineering Tool, select 'Network' task card > 'Global system configuration' > 'FS20 network configuration' > 'Ethernet sub-net' > 'Connections' > 'Station with the FN2012-A1'. –...
  • Page 106: Fn2012-A1 Web Interface

    Commissioning Ethernet switch (modular) FN2012-A1 FN2012-A1 web interface 24.3 FN2012-A1 web interface 24.3.1 Commissioning a web interface WARNING Changing the initial password When you first access the web interface, change the initial login password. If you do not change the initial password, the security of the web interface cannot be guaranteed.
  • Page 107: Changing The Ip Address

    Commissioning Ethernet switch (modular) FN2012-A1 FN2012-A1 web interface 24.3.2 Changing the IP address When commissioning a standalone FN2012-A1, you must pre-configure the IP address using the rotary switch. After that, you can assign an IP address to the FN2012-A1 that cannot be pre-configured with the rotary switch. Configuring the IP address manually ϖ...
  • Page 108: Configuring The Redundancy Role

    Commissioning Ethernet switch (modular) FN2012-A1 FN2012-A1 web interface 24.3.3 Configuring the redundancy role Where an integrated FN2012-A1 is connected to the station, redundancy management must be configured in Engineering Tool. It cannot be configured in the web interface of the FN2012-A1. ϖ...
  • Page 109: Activating Fault Monitoring For Local Ports

    3. For local ports P2 to P5, select the appropriate type of fault monitoring: 'None', 'Link up', or 'Link down'. – Activate 'Link down' monitoring for all the ports to which FS20 stations have been connected. Do not activate fault monitoring for local ports to which a management station has been connected.
  • Page 110: Restarting And Resetting The Fn2012-A1

    Commissioning Ethernet switch (modular) FN2012-A1 Restarting and resetting the FN2012-A1 24.4 Restarting and resetting the FN2012-A1 Via the web interface You can perform the following resets on the 'Product' tab: ● Restart device: Click on 'Reset device'. – The configuration is retained. ●...
  • Page 111: Commissioning The Sounder Base Fdsb291

    Commissioning the sounder base FDSB291 25 Commissioning the sounder base FDSB291 If the product version of the sounder base FDSB291 or of the fire detector in the sounder base FDSB291 is <30, then the 'Base sounder' element is not automatically created when the FDnet devices are read in. If this is the case, then you must create the 'Base sounder' element manually.
  • Page 112: Commissioning The Fire Brigade Periphery Module Fci2001-D1

    Commissioning the fire brigade periphery module FCI2001-D1 26 Commissioning the fire brigade periphery module FCI2001-D1 The fire brigade periphery module FCI2001-D1 monitors the monitored inputs and outputs for short-circuit and open line. The resistance values of the lines may be read in and stored at the push of a button.
  • Page 113: Commissioning Of I/O Card (Remote Transmission) Fci2007-A1 And I/O Card (Horn/Monitored) Fci2009-A1

    Commissioning of I/O card (remote transmission) FCI2007-A1 and I/O card (horn/monitored) FCI2009-A1 27 Commissioning of I/O card (remote transmission) FCI2007-A1 and I/O card (horn/monitored) FCI2009-A1 With the I/O card (remote transmission) FCI2007-A1 and I/O card (horn / monitored) FCI2009-A1, the monitored outputs are monitored for short-circuit and open line.
  • Page 114: Commissioning External Printer

    The external FUJITSU DL3750+ printer can be installed and commissioned using the operating manual. The operating manual is on the CD delivered with the printer. To operate the printer on the fire detection system FS20 settings that differ from the default values must be made in the following functions. ●...
  • Page 115 Commissioning external printer Function Value MENU 2 EMULATE DPL24C+ FONT COUR 10 QUALITY LETTER PITCH 10 CPI LINE SP 6 LPI CHAR-W NORMAL CHAR-H NORMAL ATTRIB NONE PAGE LG 11.0 IN LFT-END 1 COLM TOP-MRG 1 LINE LANGUAGE PAGE437 CHR-SET SET2 PRF-SKP NO-SKIP...
  • Page 116 Commissioning external printer Function Value ADJUST CNT-ORG 1 /6 IN CNTFINE 1 /180 CUT-ORG 1 /6 IN CUTFINE 1 /180 CNT-LFT 0 /90 CUT-LFT 0 /90 CUT-ADJ 0 /360 CNT-ADJ 0 /360 CNTADJL 0 /360 ==END== CONFIG TEAROFF AUTO TEARPOS VISIBLE TEAR-EN 4 SEC...
  • Page 117: Updating The Firmware

    Updating the firmware Preparation and security 29 Updating the firmware 29.1 Preparation and security WARNING Fire detection installation is deactivated during the firmware update Fire may spread unhindered. ● Supervision by people is required. ● Re-activate the fire detection installation as soon as possible. NOTICE Data loss during the firmware update Configuration data, event memory in the 'Station' and specific system data that is...
  • Page 118: Station: Updating The Fw Of The Main Cpu And Additional Cpus

    Updating the firmware Station: Updating the FW of the main CPU and additional CPUs ● The procedure for updating the firmware depends on the 'Station' configuration. A 'Station' can be configured as follows: – ↑ Standalone Station – ↑ SAFEDLINK Station –...
  • Page 119: Router Station And Ethernet Station

    Updating the firmware Station: Updating the FW of the main CPU and additional CPUs 8. Test the firmware version on the additional CPUs. Link [➙ 137] – Update the firmware, if required, of the additional CPUs again, if there is a higher firmware version available.
  • Page 120: Modular Station With Cpu Card

    Updating the firmware Station: Updating the FW of the main CPU and additional CPUs 29.2.3 Modular station with CPU card You will find additional information about the individual steps on the specified pages. ϖ You are familiar with the information in chapter 'Preparation and security [➙...
  • Page 121: Updating Several 'Stations' Simultaneously

    Updating the firmware Station: Updating the FW of the main CPU and additional CPUs 29.2.4 Updating several 'Stations' simultaneously You can update the firmware of max. eight networked ↑ 'Stations' and ↑ CPU cards simultaneously. The 'Stations' and the CPU cards must be connected to one another via FCnet/LAN.
  • Page 122: Fw Update For Main Cpu And Additional Cpus

    Updating the firmware Station: Updating the FW of the main CPU and additional CPUs 29.2.5 FW update for main CPU and additional CPUs The procedure for updating the main CPU and additional CPUs depends on whether the PMI & mainboard FCM2004, FCM2027 or the CPU card FCC2004 is used in the 'Station'.
  • Page 123 Updating the firmware Station: Updating the FW of the main CPU and additional CPUs Starting the firmware update at the 'Station' – FCM2004 1. Select 'Initiate update at station'.  The following window is opened: 2. Set the 'S38-2' switch to 'ON' on the rear of the operating unit. 3.
  • Page 124 Updating the firmware Station: Updating the FW of the main CPU and additional CPUs 4. Click on 'OK' in the 'Information' window.  The following window is opened: 5. Select 'Run in background' in order to run the firmware update in the background while continuing to work in SintesoWorks.
  • Page 125 Updating the firmware Station: Updating the FW of the main CPU and additional CPUs 29.2.5.2 PMI & mainboard FCM2027 ϖ You are familiar with the information in chapter 'Preparation and security [➙ 117]'. 1. Select 'Update' > 'FW update main and additional CPUs' from the menu bar. 2.
  • Page 126 Updating the firmware Station: Updating the FW of the main CPU and additional CPUs Starting the firmware update at the 'Station' – FCM2027 1. Select 'Initiate update at station'.  The following window is opened: 2. Keep the 'S32' button on the rear of the operating unit pressed and press <Acknowledge>...
  • Page 127 Updating the firmware Station: Updating the FW of the main CPU and additional CPUs 3. Click on 'OK' in the 'Information' window.  The following window is opened: 4. Select 'Run in background' in order to run the firmware update in the background while continuing to work in SintesoWorks.
  • Page 128 Updating the firmware Station: Updating the FW of the main CPU and additional CPUs 4. Select the desired firmware version. 5. The firmware update can be started in two ways: – Start the firmware update in SintesoWorks. Link [➙ 130] –...
  • Page 129 Updating the firmware Station: Updating the FW of the main CPU and additional CPUs 3. Click on 'OK' in the 'Information' window.  The following window is opened: 4. Select 'Run in background' in order to run the firmware update in the background while continuing to work in SintesoWorks.
  • Page 130 Updating the firmware Station: Updating the FW of the main CPU and additional CPUs 29.2.5.4 Starting the firmware update in SintesoWorks 1. Select 'Initiate update from tool'. 2. Select the connection type.  The available 'Station' are displayed. 3. Select the 'Station' you want. –...
  • Page 131 Updating the firmware Station: Updating the FW of the main CPU and additional CPUs 5. Confirm the firmware update with 'Yes' or reject the firmware update with 'No'.  The following window is opened: 6. Click on 'OK'.  The following window is opened: 7.
  • Page 132: Station: Updating The Fw Of The Additional Cpus Only

    Updating the firmware Station: Updating the FW of the additional CPUs only 29.2.5.5 Error during firmware update If errors occur during the firmware update, the error messages are shown after the update on the 'Station' display. The line 'Press Silence buzzer button' is displayed after the error messages.
  • Page 133: Router Station And Ethernet Station

    Updating the firmware Station: Updating the FW of the additional CPUs only 29.3.2 Router station and Ethernet station You can update the additional CPUs in a networked ↑ 'Station' via FCnet/LAN. In this way, you can update networked 'Stations' without disconnecting the network connection and restoring the factory setting.
  • Page 134: Fw Update For Additional Cpus

    Updating the firmware Station: Updating the FW of the additional CPUs only 29.3.3 FW update for additional CPUs NOTICE Updating the firmware of the degraded mode module FN2001 If the firmware of the degraded mode module FN2001 has to be updated, it must be temporarily connected to the slot for the main module FN2001 (from slot X12 to X13).
  • Page 135: Update Only The Bdv

    Updating the firmware Update only the BDV 10. Press <Acknowledge> on the Person Machine Interface to switch off the 'Buzzer'. Do not perform any more actions on the 'Station' until the 'Buzzer' has sounded for the second time. 11. Click on 'Close' in the 'FW update additional CPUs' window. See also 1 Preparation and security [➙...
  • Page 136: Router Station And Ethernet Station

    Updating the firmware Converting the configuration 29.4.2 Router station and Ethernet station You will find additional information about the individual steps on the specified pages. ϖ Familiarize yourself with the information in 'Preparation and security [➙ 117]'. 1. Import the new ↑ BDV into SintesoWorks. –...
  • Page 137: Testing The Firmware Version Of The Additional Cpus

    Updating the firmware Testing the firmware version of the additional CPUs 29.6 Testing the firmware version of the additional CPUs If you have updated the firmware of the main CPU and the additional CPUs in a single step ('FW update main and additional CPUs'), you must then test the firmware version of the additional CPUs to ensure that the CPUs were updated correctly.
  • Page 138: Creating Diagnosis Report

    Updating the firmware Creating diagnosis report 29.7 Creating diagnosis report To update the firmware versions for the creation of the diagnosis report, the configuration data must be loaded in SintesoWorks. ϖ The configuration data for the ↑ 'Station' is loaded to SintesoWorks. 1.
  • Page 139: Mcl-Usb Adapter Fduz22X

    Updating the firmware Updating the FW of the peripheral devices 29.8.1 MCL-USB adapter FDUZ22x The firmware of the MCL-USB adapter FDUZ221 or the MCL-USB adapter (radio) FDUZ227 must be updated if a new firmware version is issued. Preparation ϖ The driver for the MCL-USB adapter is installed on the PC. 1.
  • Page 140: Floor Repeater Terminal Ft2010

    Updating the firmware Updating the FW of the peripheral devices 29.8.2 Floor repeater terminal FT2010 WARNING Incorrect assignment between detector/detector zone and customer text Misleading messages in the event of an alarm ● Never change the wiring during the firmware update. The firmware must be updated individually for each ↑...
  • Page 141 Updating the firmware Updating the FW of the peripheral devices Updating the firmware Check the COM port setting under 'Options' > 'Preferences' > 'Periphery update' before performing the firmware update. 1. Select 'Update' > 'Periphery update wizard'. 2. In the 'Password check' window, enter the password '1234' and click on the 'Next' button.
  • Page 142: Floor Repeater Display Ft2011

    Updating the firmware Updating the FW of the peripheral devices 29.8.3 Floor repeater display FT2011 WARNING Incorrect assignment between detector/detector zone and customer text Misleading messages in the event of an alarm ● Never change the wiring during the firmware update. The firmware must be updated individually for each ↑...
  • Page 143 Updating the firmware Updating the FW of the peripheral devices Updating the firmware Check the COM port setting under 'Options' > 'Preferences' > 'Periphery update' before performing the firmware update. 1. Select 'Update' > 'Periphery update wizard'. 2. In the 'Password check' window, enter the password '1234' and click on the 'Next' button.
  • Page 144: Mimic Display Driver Ft2001-A1

    Updating the firmware Updating the FW of the peripheral devices 29.8.4 Mimic display driver FT2001-A1 WARNING Incorrect assignment between detector/detector zone and customer text Misleading messages in the event of an alarm ● Never change the wiring during the firmware update. The firmware must be updated individually for each mimic display driver.
  • Page 145 Updating the firmware Updating the FW of the peripheral devices Updating the firmware Check the COM port setting under 'Options' > 'Preferences' > 'Periphery update' before performing the firmware update. 1. Select 'Update' > 'Periphery update wizard'. 2. In the 'Password check' window, enter the password '1234' and click on the 'Next' button.
  • Page 146 Updating the firmware Updating the FW of the peripheral devices Manually setting device to update mode Proceed as follows if you are prompted to manually set the device to update mode in step 3: 1. Set the DIP switch S200-1 to 'ON'. ...
  • Page 147: Radio Gateway Fdcw221

    Updating the firmware Updating the FW of the peripheral devices 29.8.5 Radio gateway FDCW221 WARNING Incorrect assignment between detector/detector zone and customer text Misleading messages in the event of an alarm ● Never change the wiring during the firmware update. ●...
  • Page 148: Radio Gateway Fdcw221

    Updating the firmware Updating the FW of the peripheral devices Updating the firmware Check the COM port setting under 'Options' > 'Preferences' > 'Periphery update' before performing the firmware update. 1. Select 'Update' > 'Periphery update wizard'. 2. In the 'Password check' window, enter the password '1234' and click on the 'Next' button.
  • Page 149: Service Device Fdud29X

    Intelligent detector tester FDUD293 Service devices FDUD29x with firmware version <2.0 must be updated to firmware version 2.0. To do this, contact your Siemens contact partner. From firmware version 2.0, it is possible to update firmware as described below. Preparation ϖ...
  • Page 150: Line Tester Fdul221

    Updating the firmware Updating the FW of the peripheral devices 4. Click on 'Next'.  The firmware update is carried out.  The FDUD29x restarts. 5. Remove the MCL-USB adapter.  The firmware is updated. 29.8.8 Line tester FDUL221 This chapter relates to the line tester FDUL221, device version with USB connection or MC link connection, order no.
  • Page 151 Updating the firmware Updating the FW of the peripheral devices Connection to PC via FDUZ22x ϖ The driver for the MCL-USB adapter FDUZ221 or FDUZ227 is installed on the ϖ The line tester is fed either internally with batteries or via a mains adapter. Connect the device to the PC via the MCL-USB adapter.
  • Page 152 Updating the firmware Updating the FW of the peripheral devices Updating the firmware Check the COM port setting under 'Options' > 'Preferences' > 'Periphery update' before performing the firmware update. 1. Select 'Update' > 'Periphery update wizard'. 2. In the 'Password check' window, enter the password '1234' and click on the 'Next' button.
  • Page 153: Line Tester With Serial Interface Fdul221

    Updating the firmware Updating the FW of the peripheral devices 29.8.9 Line tester with serial interface FDUL221 This chapter relates to the line tester FDUL221, device version with RS232 connection, order no. up to A5Q00004397 02. Preparation ϖ The line tester is supplied via a mains adapter. ϖ...
  • Page 154: Updating The Fw Of Ethernet Switch (Modular) Fn2012-A1

    Updating the firmware Updating the FW of Ethernet switch (modular) FN2012-A1 4. Press and hold down the '▲', '▼', and '√' buttons on the line tester and click on the 'Next' button in the Engineering Tool at the same time. 5.
  • Page 155 Updating the firmware Updating the FW of Ethernet switch (modular) FN2012-A1 Updating the firmware in the web interface ϖ The FN2012-A1 has a valid IP address within the sub-net. ϖ The PC has access to the FN2012-A1 / is located within the same sub-net as the FN2012-A1.
  • Page 156 Fatal FAULT ● Carry out a reset. If unsuccessful, there is a hardware fault. ● Replace Ethernet switch. Check whether other error messages are displayed in the FS20 system. Table 7: Troubleshooting 156 | 188 Building Technologies 009052_s_en_-- Fire Safety...
  • Page 157: Fn2012-A1 Integrated Into Station

    Updating the firmware Updating the FW of Ethernet switch (modular) FN2012-A1 29.9.2 FN2012-A1 integrated into station ϖ The FN2012-A1 is connected to the station via a ribbon cable. ϖ The FN2012-A1 is connected to the sub-net via an Ethernet cable. ϖ...
  • Page 158: Maintenance

    Do not unnecessarily switch off the 'Site' or parts thereof for long periods of time. 30.2 Testing FS20 offers various test functions for efficient testing of devices and logical functions. Some test methods can be combined, others have to be carried out individually.
  • Page 159: Testing And Measuring Instruments

    Maintenance Testing and measuring instruments 30.3 Testing and measuring instruments The following table shows an overview of the testing and measuring instruments used. Test Required auxiliaries Comment Universal measuring instrument Measuring ranges: Voltage, current and resistance measuring ● Voltage: AC/DC 1…500 V ●...
  • Page 160: Preparatory Work

    Maintenance Preparatory work 30.4 Preparatory work Inform the system owner Inform the system owner of the scope and expected duration of work and also that ↑ 'Site' operation will be restricted. For large-scale systems fill out the system shutdown notification sheet and have this signed by the system owner.
  • Page 161: Testing The 'Station

    Maintenance Testing the 'Station' Change in use Verify whether a change of use or changes to the building have an effect on the configuration and perform the necessary corrections. Pending modification applications Check that all pending modification applications such as corrections to the diagrams or modifications to the fire brigade orientation plans have been completed.
  • Page 162: Check The Power Supply

    Maintenance Check the power supply 30.7 Check the power supply Check the current consumption 1. Measure the current consumption during 'Emergency power operation' and for alarms with the highest alarm level (local alarm and global alarm). 2. Compare the measurement values with the calculation value for emergency current capacity.
  • Page 163: Checking 'Site' Function

    Maintenance Checking 'Site' function 30.9 Checking 'Site' function Test the function of the ↑ 'Site' in the various test modes. You will find information on testing a 'Site' in the 'Testing' chapter of document 008838. See chapter 'Applicable documents'. See also 1 Applicable documents [➙...
  • Page 164: Carrying Out Final Maintenance Work

    Maintenance Carrying out final maintenance work Function Activity Interval (years) ↑ Alarm organization Check the function of the delay times t1 and t2. Activate a global alarm with an 'Automatic detector' in the 'Unmanned operation' operation mode. Activate a local and global alarm by setting a 'Manual call point' to the 'Manned operation' and 'Unmanned operation' operation modes.
  • Page 165: Repair

    WARNING Activation of fire or smoke dampers If fire or smoke dampers are connected to the FS20 via an input/output module, they may be activated when the station is switched off or when the station or detector line is restarted.
  • Page 166: Spare Parts

    Repair Spare parts 31.2 Spare parts ● You will find details for ordering spare parts for 'Stations' in document 009690. ● You will find details for ordering Detectors and accessories in document 008164. See chapter 'Applicable documents'. See also 1 Applicable documents [➙ 11] 31.3 Fault messages on the Person Machine Interface Fault messages on fire control panel FC20xx / fire terminal FT2040 Figure 14: Fault indicators on the ↑...
  • Page 167 Repair Fault messages on the Person Machine Interface LED flashes Cause What must be done ● Check remote transmission Fault / Off Remote ↑ Remote transmission has a alarm 'Fault' Fault / Off Alarm 'Fault' affecting acoustic ● Check the 'Line' for open circuit/short- device control lines circuit or end-of-line element (EOL) is...
  • Page 168: Fault Indicators On Components

    Repair Fault indicators on components Symbol Fault Cause What must be done FAULT The 'Site' has a fault ● Check if the fault LED 'Fault System' is flashing; if it is not: – Check the display – Check whether the 'Fault' control input is activated Fault System Failure of the main CPU...
  • Page 169: Communication Problems In Networked Systems

    Repair Communication problems in networked systems 31.5 Communication problems in networked systems Problem: You are unable to communicate with a ↑ 'Station' in a networked ↑ site. This may be due to the following causes. Date and time are not correct Check the date and time of the ↑...
  • Page 170: Correcting An Invalid Topology

    Repair Correcting an invalid topology 31.7 Correcting an invalid topology If the topology of a FDnet detector line is invalid, the error message 'Topology is invalid' is displayed after the ↑ detector line has been read in. The table below shows invalid topologies.
  • Page 171: Restart The Station

    Repair Restart the station 31.9 Restart the station The configuration of the ↑ 'Station' remains the same. There are the following ways in which to restart the ↑ 'Station': ● Via the menu on the display ● PMI & mainboard FCM2004 and FCM2027: With the 'S32' button ●...
  • Page 172: Restoring Factory Setting On The Station

    Repair Restoring factory setting on the station ↑ CPU card 1. Briefly press the 'S8' button on the CPU card until a 'R' is displayed on the LED matrix display. 2. As soon as the 'R' is displayed, press and hold the 'S8' button for approx. 2 s to confirm the selection.
  • Page 173 Repair Restoring factory setting on the station PMI & mainboard FCM2004 1. NOTICE! Configuration will be deleted! Save the configuration data for the 'Station' before restoring the factory setting. 2. Set the 'S38-1' switch to 'ON' on the rear of the operating unit. WARNING! It is impossible to acquire and process alarms or faults without a site configuration! Press the 'S32' button for >2 s until the ↑...
  • Page 174: Fiber-Optic Network Module Fn2006 / Fn2007 Troubleshooting Steps

    Repair Fiber-optic network module FN2006 / FN2007 troubleshooting steps ↑ CPU card 1. NOTICE! Configuration will be deleted! Save the configuration data for the 'Station' before restoring the factory setting. 2. Briefly press the 'S8' button on the CPU card several times until a 'F' is displayed on the LED matrix display.
  • Page 175 Repair Fiber-optic network module FN2006 / FN2007 troubleshooting steps 1 Normal condition Node 2 Node 1 FN2006/FN2007 FN2006/FN2007 Link2 Link1 Line1 Line2 Fail1 Fail2 Fault example zone Fail2 Fail1 Line2 Line1 Link2 Link1 Power Power A1 B1 A2 B2 B1 A1 B2 A2 VsysA VsysA FN2001...
  • Page 176 Repair Fiber-optic network module FN2006 / FN2007 troubleshooting steps 3 Break in optical fibers Node 2 Node 1 FN2006/FN2007 FN2006/FN2007 Link2 Link1 Line1 Line2 Fail1 Fail2 Fail2 Fail1 Line2 Line1 Link2 Link1 Power Power A1 B1 A2 B2 B1 A1 B2 A2 VsysA VsysA FN2001...
  • Page 177 Repair Fiber-optic network module FN2006 / FN2007 troubleshooting steps 4 Energy supply interrupted Node 2 Node 1 FN2006/FN2007 FN2006/FN2007 Link2 Link1 Line1 Line2 Fail1 Fail2 Fail2 Fail1 Line2 Line1 Link2 Link1 Power Power A1 B1 A2 B2 B1 A1 B2 A2 VsysA VsysA FN2001...
  • Page 178 Repair Fiber-optic network module FN2006 / FN2007 troubleshooting steps 6 Line 1, A1/B1 connection wrong way round Node 2 Node 1 FN2006/FN2007 FN2006/FN2007 Link2 Link1 Line1 Line2 Fail1 Fail2 Fail2 Fail1 Line2 Line1 Link2 Link1 Power Power A1 B1 A2 B2 B1 A1 B2 A2 VsysA VsysA...
  • Page 179: Glossary

    Glossary Glossary Control tree Alarm device Structure tree with control group and control. Element in the fire detection system for acoustic and/or visual alarming, e.g. alarm sounder, beacon. Abbreviation for 'Central Processing Unit'. The Alarm indicator computing unit of the fire control panel. Visual display to signal an alarm or pre-alarm.
  • Page 180 Depiction of a logical device function in the SAFEDLINK detection or control tree. The logical channel is always the bottom level in the structure tree. Physical network of an FS20 / FS720 fire detection system with the network module (SAFEDLINK) and the network cable. Loop...
  • Page 181 Glossary Stub Detector line which is only connected to the fire control panel on one side. In the event of an open line or short-circuit, it may no longer be possible for all fire detectors to communicate with the fire control panel. Visibility Defines which part of a site is visible and can be operated on a station.
  • Page 182: Index

    Index Index Connecting a sub-stub to a loop FDnet/C-NET detector line ......56 Acceptance test ..........23 Connection to the station ........24 Alarm counter ..........117 Connectivity ............ 24 AnalogPLUS detector line ......... 64 Conversion ............ 136 Converting a loop..........67 Configuration ..........
  • Page 183 Index Download center FDUL221 serial line tester URL ..............11 Updating the firmware ........153 FDUZ221 MCL-USB adapter Updating the firmware ........139 End-of-line element (EOL) FG2020 ............45 Reference measurement for Fire brigade periphery module FCI2001-D1 ..112 collective detector line ....... 59 Firewall Error message Safety module ..........
  • Page 184 Index I/O card (horn/monitored) FCI2009-A1 ....113 Main CPU I/O card (remote transmission) FCI2007-A1 ..113 Updating the firmware ........122 Indication of faults Maintenance ..........158 Component ........... 168 MCL-USB adapter Initialize Updating the firmware ........139 Station ............28 Measuring instrument ........
  • Page 185 Index Radio gateway Safety module (firewall) ........95 Updating the firmware ........147 Scalance X204 2 ..........92 Radio gateway FDCW221 ......148 Serial line tester Updating the firmware ........148 Updating the firmware ........153 Radio gateway FDCW241 ......148 Series number ..........
  • Page 186 Index Test ............91, 163 Test intervals .......... 163, 163 Test mode ............89 Detector ............89 Exit ..............90 Test unit ............159 Testing Collective detector line ........60 Detector ........87, 87, 88, 88 Detector line ........... 22 Function ............
  • Page 187 Index 187 | 188 009052_s_en_-- Building Technologies Fire Safety 2016-06-02...
  • Page 188 Issued by © Siemens Switzerland Ltd, 2006 Siemens Switzerland Ltd Technical specifications and availability subject to change without notice. Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug +41 41-724 24 24 www.siemens.com/buildingtechnologies Document ID: 009052_s_en_-- Manual FS20 Edition: 2016-06-02...

Table of Contents