Indicators; Adjustment Elements - Siemens 13-xx-ST-SBT Series Product Data

Fire detection system
Table of Contents

Advertisement

RT interface
12
Fault
13
K1
14
K1
15
K2
16
K2
17
K3
18
K3
19
K4
20
K4
48.4
LED
Color
Function
H1-1
Red
Relay 1
H1-2
Red
Relay 2
H2-1
Red
Relay 3
H2-2
Red
Relay 4
H3
Yellow
Test
48.5
Building Technologies
Fire Safety
Cable tree
White
1 (+ 2)
Black
2
Brown
2 + 3
Green
2
--
3
Gray/pink
2
--
3
--
--
--
3
Cable no.:
Cable 1 to periphery board, control cable VDE LI-CY 0.34 mm
560 mm, included in cable set
Cable 2 to RT device, control cable 14-pin VDE LI-CY 0.34 mm
700 mm, included in cable set
Cable 3 = loop made from wire jumpers 3 x 0.22 mm

Indicators

Condition
Off
On
Off
On
Off
On
Off
On
Off
On

Adjustment elements

The switching contacts of the relays K1...K4 and the 'Alarm' and 'Fault' test
contacts must be configured as 'normally open' (NO) or 'normally closed' (NC). The
application-specific configuration is made by inserting a wire jumper (0
resistance) between the corresponding solder pins.
The following figure shows a configuration example using relay K1.
K1
4 loop periphery board
X7-5
FAU_COM
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
Meaning
Quiescent condition, relay inactive
Relay activated
Quiescent condition, relay inactive
Relay activated
Quiescent condition, relay inactive
Relay activated
Quiescent condition, relay inactive
Relay activated
Quiescent condition
Test mode active (key S1 pressed)
NO
Y3
X3
NC
RT interface FCI2006-C1 [CH]
Indicators
2 loops periphery board
X7-5
FAU_COM
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
, 14-pin, length
2
, length
2
x 40 mm
2
13
14
008837_q_en_--
48
297