47.5
Building Technologies
Fire Safety

Adjustment elements

The switching contacts of the relays K1 ... K12 must be configured as 'normally
open' (NO) or 'normally closed' (NC). The application-specific settings are made by
inserting a wire jumper or a resistor between the corresponding solder pins.
The following figure shows the setting of the relay K5 as an example.
K5
Example: Setting the switching contacts
Settings
NO = wire jumper or resistor between solder pins X19 and X43
NC = wire jumper or resistor between solder pins X20 and X44
Settings for Holland (default)
Relay
Contact
K5
REL5_OUT+
K6
REL6_OUT+
K7
REL7_OUT+
K8
REL8_OUT+
RT interface FCI2005-N1 [NL]
NC
X20
X44
X43
X19
NO
Solder pins
NO/NC
X19 ... X43
NO
X20 ... X44
NC
X21 ... X45
NO
X22 ... X46
NC
X23 ... X47
NO
X24 ... X48
NC
X25 ... X49
NO
X26 ... X50
NC
47
Adjustment elements
REL5_OUT-
REL5_OUT+
Resistance
680
3.3 k
680
3.3 k
680
3.3 k
680
3.3 k