11
Operating unit with PMI & mainboard FCM2027

Adjustment elements

LED
Color
Function
H53
Yellow
'CPLD fail' (reset and watchdog logic)
H54
Red
'TEMP', CPU module excess
temperature indicator
H61
Yellow
'SPEED', Ethernet transmission
indicator
H842
Green
'LINK' control indicator
11.4
86
Building Technologies
Fire Safety
Adjustment elements
S32: Reset key
The S32 button has a number of functions depending on how long it is pressed
for and whether it is pressed in combination with other buttons.
Operation
Press for <2 s
Press for >2 s
Press S32 + 'Reset' or
'Acknowledge' (front
operating buttons) at the
same time
Restore factory settings
Operation
Press S32 + 'Reset' (front
operating button) at the
same time for >2 s
You will find detailed instructions in document 009052. See chapter 'Applicable
documents'.
Updating the firmware
Operation
Press S32 + 'Acknowledge'
(front operating button) at
the same time for >2 s
You will find detailed instructions in document 009052. See chapter 'Applicable
documents'.
Condition
Meaning
Off
Normal operation
On
Logic unit failed; replace component or
contact hotline
Not used
Off
Data transfer at 10 Mbit/s
On
Data transfer at 100 Mbit/s
Off
No Ethernet connection
On
Ethernet connection established
Function
Station is shut down and restarted in a controlled manner.
This procedure takes up to 5 minutes.
Station is shut down and restarted immediately. This may
lead to data loss. This procedure takes up to two minutes.
Restore factory settings or update firmware.
Function
Station is started in Restore factory settings mode.
A short peeping sound confirms the function is being
executed.
Function
Station's firmware is updated.
A short peeping sound confirms the function is being
executed.