25 Line card (FDnet/C-NET) FCL2001-A1
25.1
Building Technologies
Fire Safety
Description
The line card (FDnet/C-NET) FCL2001-A1 is a line card in addition to the
integrated line cards of the FS20 fire control panels. It is inserted in the fire control
panels with the card cage (5 slots) FCA2008-A1. The line card (FDnet/C-NET) has
an integrated line driver that can be used for connecting up to four loops and 252
FDnet devices. The maximum possible number of addresses per loop is 126.
The line card consists of a control part and a line driver that is electrically isolated.
The functionality of the line card (FDnet/C-NET) corresponds to the integrated line
driver of the fire control panel FC2020with a loop extension (FDnet).
The line card (FDnet/C-NET) has the following features:
Connection of four FDnet loops or eight stubs (mixed variants are possible)
Maximum of 252 device addresses per loop
Maximum of 252 device addresses per line card
Electrical isolation of the FDnet lines
Line card (FDnet/C-NET) FCL2001-A1
25
Description
145
008837_q_en_--
14.05.2012