Siemens 13-xx-ST-SBT Series Product Data page 61

Fire detection system
Table of Contents

Advertisement

Monitored output
Fault
Changeover contacts
RT alarm
Monitored output
Alarm
Monitored sounder (horn)
output
Building Technologies
Fire Safety
Designation
Design
Output voltage
Output current
Guaranteed output current
(monitored for short circuit and open line)
Monitored for
(if output inactive)
Nominal monitoring resistance
Min. tolerance
Designation
Design
Switching voltage
Switching current
Designation
Design
Output voltage
Output current
Guaranteed output current
(monitored for short circuit and open line)
Monitored for (if output inactive)
Nominal monitoring resistance with tolerance
Designation
Design
Output voltage
Output current
Guaranteed output current
(monitored for short circuit and open line)
Monitored for (if output inactive)
Nominal monitoring resistance
with tolerance
Periphery board (2 loops) FCI2002-A1
Technical data
'VSYS_O'; 'FAU_OUT'
Open drain
Failsafe
Activated in degraded mode
DC 21...28.6 V
Max. 300 mA (protected with 1 AT)
15 mA with U
= 16 V
out min
Short-circuit
Open line
1.6 ... 2.3 k
+/–
'AL_NO'; 'AL_COM'; 'AL_NC'
Relay output
Break or make contact
Activated in degraded mode
Max. DC 60 V
Max. 400 mA
'AL_OUT+'; 'AL_OUT-'
Relay reversed polarity
Activated in degraded mode
DC 21...28.6 V
Max. 1 A (protected with 1 AT)
20 mA with U
= 16 V
out min
Short-circuit
Open line
2.3...5.5 k
+/–
'SOUND1+'; 'SOUND1-'
Relay reversed polarity
Activated in degraded mode
DC 21...28.6 V
1
Max. 1 A (protected with 1 AT)
20 mA with U
= 16 V
out min
Short-circuit
Open line
2.3...5.8 k
+/–
7
61
008837_q_en_--
14.05.2012