16.4
Supply input
System bus
Connections
Mechanical data
Building Technologies
Fire Safety
Technical data
Voltage
Operating current
Voltage
Current
Impedance
Cable type
Protocol
Data rate in operation mode:
'Standard'
'Low'
Distance between 2 network modules
Electrical isolation between the FCnet and
the station
Monitored for:
Dimensions (W x H x D)
Weight
Network module (SAFEDLINK, CC) FN2010-A1
DC 21...30 V
Max. 45 mA
DC 5 V
Max. 100 mA
120
Shielded and unshielded cables
Example:
Uninet 30044PFRNC(KAT6)
R&M fseenet KAT5e F/UTP 4P
Communication cable J-
2T(St)TSTIIIBD
CCM 2C1.5T1/1254(MICC)
Fire detection cable
JY(St)Y2 x 2 x 0.8 mm red
SAFEDNET (UDP/IP)
312 kbit/s
96 kbit/s
Max. 1000 m
1 kV, limited to 45 V with respect to ground
Short-circuit
Open line
Ground fault
Communication error
2 plug connections
50 x 20 x 70 mm
20 g
16
Technical data
103
008837_q_en_--
14.05.2012