43
Fire brigade periphery module FCI2001-D1 [DE]
Technical data
Fire department key depot
Identification lamp (KL)
Local alarm (LA)
Connections
Mechanical data
248
Building Technologies
Fire Safety
Tamper input:
Design
Termination resistor for quiescent condition
Monitored for
Line resistance per wire
Deblocking output:
Voltage/current (if active)
Design
Line resistance per wire
Input latch contact:
Design
Line resistance per wire
Output heating:
Voltage/current (if active)
Design
Line resistance per wire
Output tamper transmission:
Switching voltage/switching current
Design
Voltage/current (if active)
Design of the output
Line resistance per wire
Voltage/current (if active)
Design of the output
In quiescent condition monitored for
Load resistance
Line resistance per wire
VdS peripherals
Power supply
Periphery board
Dimensions (L x W x H)
Weight
Short-circuit-proof
2.2
Deviation >40 % of 2.2
Max. 10
24 V / type 260 mA; max. 1 A
Active high
Short-circuit-proof
Current limited
Max. 5
Active low
Short-circuit-proof
Max. 10
24 V, type 200 mA (5 W); max. 1 A
Active high
Short-circuit-proof
Current limited
Max. 5
AC 30 V / 1 A max. (max. 30 W)
Quiescent current relay
Potential-free
24 V / type 300 mA; max. 1 A
Active high
Short-circuit-proof
Current limited
Max. 5
24 V / type. 12 ... 600 mA (max. 1 A)
Active high
Short-circuit-proof
Current limited
Short-circuit
Open line
40 ...2 k
Max. 5 % of the load resistance
Screw terminals; 0.2...1.5 mm²
Screw terminals; 0.5...2.5 mm²
Plug-type connection
190 x 150 x 40 mm
200 g
008837_q_en_--