Technical Data - Siemens 13-xx-ST-SBT Series Product Data

Fire detection system
Table of Contents

Advertisement

3.5 Technical data

Mains supply
Supply output (System)
Supply output (Battery)
Monitoring signal Mains fault
Monitoring signal Battery fault Designation
Connections
Mechanical data
Standards and approvals
Building Technologies
Fire Safety
Voltage
Current
Power consumption
Designation
Voltage
Current:
Maximum nominal output current
with battery charge (I
max a
Maximum nominal output current
without battery charge (I
Minimum output current (I
Performance
Ripple
Designation
Voltage
Charging current
Connectable batteries
Load resistance (R
)
imax
Batteries are monitored for
Low discharge protection
Designation
Active in event of
Design
Active in event of
Design
Designation
Active in event of
Design
Mains supply, battery supply and
monitoring signals
Dimensions (W x H x D)
Weight
Standards
Approvals
CPD certificate
CE conformity mark
Power supply (70 W) FP2001-A1
AC 85...265 V, 50/60 Hz
0.5...1 A
Max. 90 VA
'Usys'
DC 20...28.6 V (depending on charge and
temperature)
0.9 A
)
2.5 A
)
max b
)
0.05 A
min
70 W
Max. 2.5 %
'Akku'
DC 21...28.6 V (depending on charge and
temperature)
Max. 1.6 A (the charging current is reduced at full
load)
2 x 12 V / 7...17 Ah (all battery types recommended
by Siemens in acc. with document 008843)
Max. 1
(batteries incl. line)
Short-circuit
Open line
Internal short-circuit
Presence
Battery voltage < DC 20.5 V
'Main'
No mains voltage (signal within 10 s)
Open collector
'Battery'
Battery fault
Battery voltage DC <21.0 V (together with
'Main')
Open collector
'Convert'
Fault within the power supply
Open collector
Plug-type connection
95 x 170 x 54 mm
800 g
EN 54-4:1997
VdS G206112
0786-CPD-20266
Yes
3
Technical data
25
008837_q_en_--
14.05.2012

Advertisement

Table of Contents
loading

Table of Contents