Power

Note:
Before making the power connection, ensure proper voltage selection.

AC Supply Wiring

voltage switch
shown in the 'OFF'
position. Select
appropriate voltage.
Notes:
The equipment must be protected by a 15 A fuse or circuit breaker in the
building installation.
A circuit breaker or switch in the building installation, marked as the
disconnect switch, shall be in close proximity to the equipment and
within easy reach of the operator.
Never operate the AiRanger DPL Plus with the enclosure lid open, or
with the ground (earth) wire disconnected.
Ensure that any associated alarm or control equipment is disconnected
until satisfactory operation is verified.

DC Supply Wiring

Notes:
DC terminals shall be supplied from a SELV source in accordance with
IEC-1010-1 Annex H.
7ML19981BD02
33
34
35
36
37
24 V
!
BOARD B
AiRanger DPL Plus – INSTRUCTION MANUAL
34
100/115/200/230 V
50 / 60 Hz
Select voltage via switch.
33
34
35
36
37
24 V
L1
L2/N
35
36
37
Page 17