X1 Supply - Siemens 13-xx-ST-SBT Series Product Data

Fire detection system
Table of Contents

Advertisement

Remote (mimic) EVAC, 20 zones
RS485 (FCA2002-A1)
Usys (Peripherieboard 2-/4-Loop)
Wiring example for calculating the cable resistance
45.3.2
Building Technologies
Fire Safety
Example of using the diagram
Two remote EVAC-NL indicators, one with 20 zones, the other with 30 zones, are
supplied by the periphery board of the same station.
20 pin
Number of zones via the same supply cable: 50 (20 from panel 1 and 30 from
panel 2)
According to the diagram, this results in the following values for the EVAC-NL
mimic display driver:
Maximum cable resistance R' is 10
Maximum current is 0.85 A (curve 4)
In the same way, this would result in the following for a remote EVAC-NL indicator:
Maximum cable resistance R' is 22
Maximum current is 0.4 A (curve 3)

X1 supply

Pin
Designation
10
VSYS–
9
VSYS–
8
VSYS+
7
VSYS+
6
RS485_B
5
RS485_A
4
COMMON
EVAC-NL connector board FTI2002-N1 [NL]
Remote (mimic) EVAC, 30 zones
mimic display driver
FT2003-N1
X4
FTI2002-N1
Connector
board
X2
X3
X1
X5
mimic display driver
FT2003-N1
X4
FTI2002-N1
Connector
board
X2
X3
X1
X5
mimic display driver
FT2003-N1
X4
FTI2002-N1
Connector
board
X2
X3
X1
X5
(curve 1)
(curve 2)
Description
Supply input from the power supply (–)
Supply input from the power supply (–)
Supply input from the power supply (+)
Supply input from the power supply (+)
Input connection B
1
Input connection A
1
Ground
Pin assignments
FTO2007-N1
X402
Operating unit
34 pin
X400
'Master'
X1
Synoptic panel
3 x 34 pin
FTO2007-N1
X402
Operating unit
34 pin
'Slave'
X400
X1
Synoptic panel
3 x 34 pin
FTO2007-N1
X402
Operating unit
34 pin
'Slave'
X400
X1
Synoptic panel
3 x 34 pin
008837_q_en_--
14.05.2012
45
261

Advertisement