29.4
29.5
Building Technologies
Fire Safety
Indicators
Standard LED indicators
LED
Color
Function
H301
Yellow
Signal of module
bus driver
OUT1
Yellow
Status of
monitored
output 1
OUT2...7 In accordance with OUT1 to output 2...7
MSP
Yellow
Status
Line driver
Adjustment elements
Button
Meaning
CALIB
Calibration
S501
I/O card (horn/monitored) FCI2009-A1
Condition
Meaning
Off
Normal condition
Flashes slowly
Degraded mode
1 x flashing
Update begins
(every 2 s)
2 x flashing
Update running
(every 2 s)
3 x flashing
Update failed
(every 2 s)
Flashes rapidly
Incorrect test, update needed
Off
Normal operation
Slow
Fault:
Connection interrupted or
short-circuited
(Priority 2)
Fast
Fault:
Overload fuse active
(Priority 1)
Pulsating
- Calibration invalid
- Calibration running
(maximum 25 seconds)
(Priority 3)
On
Output activated
(Priority 4)
Off
Normal operation
Slow
Line driver in degraded mode
(Priority 2)
Fast
General fault (Priority 1)
Pulsating
On
Function
Starts the calibration of the
monitored outputs
29
Indicators
169
008837_q_en_--