Ef1/Ef2 Sockets For Safdlink Networking - Siemens 13-xx-ST-SBT Series Product Data

Fire detection system
Table of Contents

Advertisement

17
Fiber optic network module FN2006 / FN2007
Pin assignments
17.3.2
106
Building Technologies
Fire Safety
The power supply need not be monitored and made redundant when installing
in the fire control panel.
The supply line must be shielded with remote networking module.
Relay contact opens in the event of an error. The display indicates the error
(COM and NC are connected).
1 2 3 4 5
+ -
C NO NC
Terminal Plug
without housing
Connector for Power A and Power B sockets

EF1/EF2 sockets for SAFDLINK networking

The 3-pin connector for the FCnet/SAFEDLINK connection is supplied with the
fiber optic cable network module.
The total cable lengths of the electric FCnet connections (copper cable) in the
optical network may not be longer than 1000 m.
Connector
Cover cap (open)
360º shielding
Terminal Plug
with housing
008837_q_en_--
14.05.2012