Indicators - Siemens 13-xx-ST-SBT Series Product Data

Fire detection system
Table of Contents

Advertisement

5.4 Indicators

LED
Color
Function
H1
Green
Monitoring of voltage
surveillance
H2
Yellow
Monitoring of battery On
H3
Yellow
monitoring of
temperature sensor
Building Technologies
Fire Safety
1
Cable tree to periphery board or fire terminal board
2
Existing cable tree (connection for master power supply)
3
Additional cable tree for the second power supply (slave 1)
4
Additional fused terminal (F2) on the DIN rail
5
Additional cable tree for the third power supply (slave 2)
The connection lines marked in bold of the additional cable tree (3 and 5) and
the existing cable tree (2) must be wired again when installing the second
power supply (slave).
In order to avoid ambient temperature differences, the three power supply units
must be mounted next to each other in the same housing.
The batteries and the system supply must only be connected to the master
power supply unit.
Only one temperature sensor must be connected to the master power supply
unit.
The temperature sensor must be fitted close to the batteries. (You will find
precise details in document 008851).
NOTICE
Damage to the power supply
Different versions (A4/A5) of the power supply (150 W) may not be switched in
parallel.
Condition
On
Off
Off
On
Off
Power supply (150 W) SV 24V-150W-A5
Meaning
Normal operation (mains voltage available)
Fault (no mains voltage)
Battery fault (open line, short circuit or voltage too low)
Normal operation (no fault)
Temperature sensor fault (open line, short-circuit or excess
temperature)
Normal operation (no fault)
5
Indicators
41
008837_q_en_--
14.05.2012