Parts of the H-S81-HS System

Field Connections

BR1 Terminal Block
It is a 12-way terminal block to connect the ten default inputs and the local fire alarm sounder.
CAUTION:
!
THE REMOTE EVACUATION CONTROL AND REMOTE CONTROL PANEL RESET INPUTS
MUST NOT BE ACTUATED DIRECTLY THROUGH EXTERNAL MANUAL BUTTONS SINCE THEY
ARE NOT MONITORED. THIS GUARANTEES COMPLIANCE WITH STANDARD EN-54-2.
98
M11
K11
M12
K12
M13
K13
M14
K14
M15
K15
M16
K16
BR1
Function
M1
Remote buzzer silencing input
M2
Remote sounder silencing input
M3
Remote control panel reset input
M4
Remote evacuation control input
M5
Battery status input (supply/charge)
M6
PSU1 primary power supply trouble input
M7
PSU2 secondary power supply trouble input
M8
Battery charge status (Full charge/Trickle)
M9
External Fault Input
M10
Revolving door tamper input
M11
Local sounder/buzzer output +
M12
Local sounder/buzzer output -
EN-54-2 COMPLIANCE
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Currently not used
Running System
System fault
System
Power supply fault
CPU fault
Control panel reset
Type
Safety
Safety
Safety
Safety
System
System
System
System
Safety
Security
Safety
Safety
Termination modules
Normally energized
Normally energized
Normally energized
Normally energized
Normally energized
Pulsing on reset
Notes
N.O.
N.O.
N.O.
N.O.
0V during charge
N.C.
N.C.
0V full charge
N.C
N.C
max. 250mA
max. 250mA