Section 3: Installation; Positioning Of The Control Panel; Measures For Installation In Compliance With The Ec Standard; Mounting The H-S81-Hs-1R & H-S81-Hs-2R Control Panels - Honeywell H-S81-HS Operation Manual

Industrial fire panel
Hide thumbs Also See for H-S81-HS:
Table of Contents

Advertisement

This chapter provides all the necessary information for proper product installation.
NOTE: All operations described in this chapter must be carried out by certified personnel.

3.1 Positioning of the Control Panel

Before positioning the H-S81-HS control panel, please refer to the environmental specifications for
proper product operation described in Section 1.3. The control panel must be located in a properly
monitored area and in a place granting easy access to the staff.
NOTE: All the parts used in H-S81-HS systems are selected depending on the relevant intended
use and are suitable for operating in compliance with the technical specifications and the relevant
environmental conditions therein specified.
3.2 Measures for Installation in Compliance with the EC
Standard
For proper system installation on the steelwork, undertake the following measures:
Use only power supply sets certified for the product.
Lay power cables and terminating cables of field devices on two separate paths.
Use shielded cables to connect field devices and I/O modules.
Follow all the instructions provided for system earthing.
In case of permanent installation, the electrical system of the building must be provided with a
(magnetothermal/differential) disconnect device, easy to be accessed and with the following
features:
Power Supply Set
S81-PU001-1
S81-PU001-2
S81-PU001-4
S81-PU002-2
S81-PU002-4
3.3 Mounting the H-S81-HS-1R & H-S81-HS-2R Control Panels
Figure 3.1 Wall Mounting
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015

Section 3: Installation

Max. Absorbed Current at
110VAC
1.6A
3.3A
6.4A
6A
12A
The control panel must be located in an easily accessible
place, well signaled and protected against fire. To mount
the steelwork to the wall (H-S81-HS-1R, H-S81-HS-2R)
use the four tabs provided. To mount it to masonry walls,
use Fisher-like nylon expansion anchors of at least 8mm.
Electrical
Type of Protection
Characteristics
6A-400VAC
10A-400VAC
Magnetothermal
12A-400VAC
differential switch
12A-400VAC
20A-400VAC
105