Configuration; Field Connections; S81-T8008-1 - Honeywell H-S81-HS Operation Manual

Industrial fire panel
Hide thumbs Also See for H-S81-HS:
Table of Contents

Advertisement

I/O modules

Configuration

By using the configuration program ProS81, the following parameters can be set for each output
channel:
Function
Operating mode
Timing
Output type
Output status in case of CPU fault
Enable/Disable status export to Hosts
Enable/Disable commands from Hosts on
the channel

Field Connections

The module can be connected to field terminal block by using a flat or a multi-conductor cable,
depending on the used bus type.
S81-E2001-1 Bus
Thanks to this bus, the module can be terminated by using a S81-T8001-1
termination module with 16 terminals.
S81-E2001-2 Bus
Thanks to this bus, the module can be terminated by using a S81-CCT1
16-conductor multi-polar cable or a S81-T8008-1 module.

S81-T8008-1

Should 500 mA per line not be enough, it is possible to connect the optional module S81-T8008-1
to module S81-F5003-1. The former will add 4 x 2A at 24 VDC polarity reversal outputs.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Mode
Continuous-Normally Energized, Continuous-Normally de-energized, Intermittent,
Pulsing-1, Pulsing-2, ISA-1A Alarm Sequence, Delayed on activation, Delayed on
enabling, Delayed on deactivation, ANSI-S3.41, March
1 to 255 seconds
Normal / Sounder
Frozen in the last status / Off
No, TCP1, TCP2, RS232
No, TCP1, TCP2, RS232
Parts of the H-S81-HS System
65