I/O modules
Status Indications
The front panel includes 8 LEDs with the following functions:
LED
Active (Red LED)
Disabled (Yellow LED)
Fault (Yellow LED)
Loop Fault (Yellow LED)
Log on Fault (Yellow LED) Flashing in case of difference between the detected devices and the programmed ones.
Service (Yellow LED)
TX Pol. (Green LED)
RX Pol. (Green LED)

Configuration

By using the configuration program ProS81, the following parameters can be set for each point of
the single devices, according to the relevant type:
Parameter
Operating mode
Measuring range
Pre-alarm threshold
Alarm threshold
Type of indication
Automatic alarm reset
Operating mode
Timing
Enable/Disable status export to
Hosts
Enable/Disable commands from
Hosts on the channel
The following measuring ranges, with the relevant thresholds, can be programmed for S81-Mod-
AI020, S81-Mod-AV010 analog modules:
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Indication
Steady on if an input is under alarmed/activated condition
Steady on if an input or an output is disabled
Flashing in case of Fault condition
Flashing in case of loop short circuit or open loop
Flashing in case of in case of smoke detectors with dirty lenses
It lights up every time data are transmitted from the module to loop devices.
It lights up every time data from loop devices are received
Type
Mode
Sensors
Latching-NO, Latching-NC, Non-Latching-NO, Non-Latching-NC
Sensors
See table
Sensors
According to the selected measuring range
Sensors
According to the selected measuring range
Sensors
Fire, Supervisory, Gas, Trouble, Hidden, Buzzer Only
Sensors
Yes/No
Actuators
Continuous-Normally Energized, Continuous-Normally De-energized,
Intermittent, Pulsing
Actuators
1 to 255 seconds (only for pulsing and intermittent modes)
Sensors/Actuators No, TCP1, TCP2, RS232
Sensors/Actuators No, TCP1, TCP2, RS232
Measuring Range Pre-alarm Threshold Alarm Threshold
0-255 Bit
0-255
0-10 ppm
0.0-10.0
0-20 ppm
0.0-20.0
0-50 ppm
0.0-50.0
0-100 ppm
0-100
0-200 ppm
0-200
0-500 ppm
0-500
0-999 ppm
0-999
0-100%LEL
0-100
0-25%O2
0.0-25.0
15-25%O2
15.0-25.0
4-20 mA
4.0-20.0
0-100 °C
0-100
0-150 °C
0-150
0-10 V
0.0-10.0
Parts of the H-S81-HS System
0-255
0.0-10.0
0.0-20.0
0.0-50.0
0-100
0-200
0-500
0-999
0-100
0.0-25.0
15.0-25.0
4.0-20.0
0-100
0-150
0.0-10.0
77