Addressing Velociti SLC Devices

5.7 Addressing Velociti SLC Devices
All Velociti devices are addressed using the two rotary dials that appear on the device board. Use the ONES rotary dial to set the ones
place in a one or two digit number, and use the TENS rotary dial to set the tens place in a two digit number.
The control panel recognizes when an Velociti detector or Velociti module is installed. For this reason, Velociti detectors can be assigned
any unique Address from 1 to 75, and Velociti modules can be assigned any unique Address from 1 to 75. There can be an Velociti detec-
tor using Address 1 and an Velociti module using Address 1. 0 is an invalid Address.
NOTE: The control panel will not identify any device addressed over 50.
Example 1: To select device Address 1, turn the ONES rotary dial to 1 and the TENS rotary dial to 0 as shown in Figure 5.5.
Example 2: To select device Address 42, turn the ONES rotary dial to 2 and the TENS rotary dial to 4 as show in Figure 5.5.
Example 1: Device Set to 01.
5.7.1 SLC Devices with DIP Switches
Input and relay module addresses are set using the DIP switches on the module board. The chart below shows the available addresses.
For example, to select Address 3, place DIP switches 1 and 2 in the Up position. The range of valid addresses is 1-50. 0 is an invalid
address.
NOTE: Any device addressed over 50 will not be recognized by the panel.

5.8 Wiring the VW-GATE

NOTE 1: The VW-GATE, as part of the wireless network, has been tested for compliance with the Federal Communications Commission
(FCC) requirements of the United States Government. It has not been evaluated for use outside the USA. Use of this system outside the
USA is subject to local laws and rules to which this product may not conform. It is the sole responsibility of the user to determine if this
product may be legally used outside the USA.
NOTE 2: It is recommended to use the same wire gauge is there are multiple connections to the same terminal.
For more information regarding Gateway wiring instructions, see SWIFT manual LS10036-000GF-E.
5.8.1 SLC Connections
The VW-GATE Wireless Gateway acts as a bridge between a group of wireless fire devices and a SLC loop on the GWF-7075. It is pow-
ered by the SLC loops or by a regulated, external 24 VDC UL listed power supply. See Section 5.2 for a list of available wireless
devices. For details about wireless devices, system setup, and operation, see the SWIFT
Instruction Manual P/N LS10036-000GF-E.
GWF-7075 Manual - P/N LS10147-002GF-E:E 06/11/2019
Example 2: Device Set to 42.
Figure 5.5 Velociti SLC Device Addressing Using Rotary Dials
Figure 5.6 SLC Device Addressing Using DIP Switches