Configuration
The first line shows module type and position and channel number. The second line shows the
alarm threshold, with the unit of measure. The third line shows the pre-alarm threshold, with the
unit of measure. The fourth line shows the lower trouble threshold in milliamperes. The fifth line
shows the gas percentage of the calibration mixture. On the bottom of the screen, the allowed range
for each one of the 4 adjustable parameters is displayed. After changing the values, go to the field
Update Parameters and press Enter for sending the new parameters to the module.

7.10.2 Fire Extinguishing Modules

Selecting this option, the stage of fire extinguishing zone parameter adjustment for S81-F6001 type
modules will be accessed. First of all, enter the rack number and the position of the module whose
parameters are to be changed. If the module does not exist, or is of a different type, an error mes-
sage is displayed. If the entered module exists and the relevant type is correct, the screen below will
be displayed.
The first adjustable parameter is the release delay. A value range of 0 to 60 can be set. The second
parameter is the inhibit time of release activation and sequence start conditions reset. A value range
of 1 to 30 can be set. The third parameter is the operating mode of the Hold function. In mode A,
the Hold condition does not interrupt the discharge delay time count; in mode B the Hold condition
resets the discharge delay time; in mode C, the Hold condition interrupts the discharge delay time
count 10 seconds before it is over. Parameters can be changed by using the arrow buttons as fol-
lows:
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Figure 7.16 4-20mA Modules
Figure 7.17 Fire Extinguishing Modules
Operating Instructions