Wiring The Fwsg; 1: Slc Connections - Honeywell Notifier AFP-100 Wiring Manual

Intelligent control panel slc
Table of Contents

Advertisement

Intelligent Detectors, Intelligent Detector Bases, and Wireless Gateway
Installation, Programming, and Addressing
CLIP loop limitations
–Detectors per CLIP loop
–Modules per loop
Power supply
FlashScan Loop Protocol
–Type ID
–FlashScan Type ID
CLIP Loop Protocol.
–Type ID
Setting an SLC Address

10.7 Wiring the FWSG

NOTE: The FWSG as part of the wireless network has been tested for compliance with the Federal
Communications Commission (FCC) requirements of the United States Government. This product has not been
evaluated for use outside the USA. Use of this system outside the USA is subject to local laws and rules to which
this product may not conform. It is the sole responsibility of the user to determine if this product may be legally
used outside the USA.
10.7.1 SLC Connections
The Wireless Gateway acts as a bridge between a group of wireless fire devices and a FlashScan SLC loop on NFS-320, NFS-320SYS,
NFS2-640, and NFS2-3030. It is powered by the SLC loop or by an external 24 VDC UL-listed power supply. Available wireless devices
include a photo detector, a photo/heat detector, a fixed-temperature heat detector, a rate-of-rise heat detector, and a monitor module. For
details about wireless devices, system setup, and operation, see the SWIFT™ Smart Wireless Integrated Technology Instruction Manual.
54
SLC
Connection
24V External
From Power Supply or Previous Device +
Power
From Power Supply or Previous Device -
Figure 10.9 FSA-20000/FSA-20000P Connection to the FACP
FSA-5000
Intelligent
FAAST XS
Not available
FACP AUX or use a power supply ULC listed for fire protective signaling use with regulated outputs
–Aspiration
–FAASTX
Not available
The SLC loop address for this product is set using PipeIQ®; for information on this program, refer to the
FAAST Comprehensive User Guide on http://www.systemsensor.com. To program the addressable pipes on
the Intelligent FAAST XT PRO, use VeriFire Tools.
Table 10.1 Installation Considerations and Programming Options
To Next SLC Device -
From FACP or Previous Device -
To Next SLC Device +
From FACP or Previous Device +
To Next Device +
To Next Device -
FSA-8000
Intelligent
FAAST XM
–Up to 75 total
Not available
–Up to 45 total
–Aspiration
–Aspiration
–FAAST
–FAASTX
–Acclimate
Not available
Notifier SLC Wiring Manual — P/N 51253:U5 12/20/2017
Wiring the FWSG
FSA-20000
FSA-20000P
Intelligent
Intelligent
FAAST XT
FAAST XT PRO
Not available
–Aspiration
–FAASTX
Not available