9: S81-F6001-1; Description; Technical Features; Status Indications - Honeywell H-S81-HS Operation Manual

Industrial fire panel
Hide thumbs Also See for H-S81-HS:
Table of Contents

Advertisement

I/O modules
2.4.9 S81-F6001-1

Status Indications

The front panel includes 8 status LEDs with the following functions:
LED
Activated (Red LED)
Relised (Red LED)
Fault (Yellow LED)
Disabled (Yellow LED)
Inhibit (Yellow LED)
Hold (Yellow LED)
Aut. Off (Yellow LED)
Res. Bank (Yellow LED) Steady on when the reserve bank is selected

Virtual channels

The module controls the following variables:
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015

Description

This module is used for controlling the logic and indications of a certain fire
extinguishing zone in compliance with the requirements of the EN12094-1 stan-
dard. It controls ten output variables and seven input variables. It controls some
fire extinguishing system typical logics, such as discharge delay and reset inhibit
time. This module checks the status of the inputs and outputs physically located
on other modules by using virtual channels.

Technical Features

• Safety rating:
• Redundancy:
• Max. output current
• Automatic output protection:
• Supply voltage:
• Quiescent current:
• Operating temperature:
• Storage temperature:
• Maximum humidity:
• Hot swap capability:
Indication
Steady on under "activated" condition. It goes out in case of reset.
Steady on under "released" condition. It goes out in case of reset.
Flashing in case of trouble in the fire extinguishing zone.
Steady on if a fire extinguishing zone is disabled
Steady on under "inhibit" condition.
Steady on under "Hold" condition.
Steady on under "Automatic exclusion" condition
Variable
Type
Description
V1
In
"Activated" condition
V2
In
Main primary discharge
V3
In
Reserve primary discharge
V4
In
Main secondary discharge
V5
In
Reserve secondary discharge
V6
In
Intermittent audible indications
V7
In
Continuous audible indications
V1
Out
Manual activation
V2
Out
Automatic activation
V3
Out
Automatic exclusion
V4
Out
Emergency hold
V5
Out
Release inhibition
V6
Out
Reserve bank
V7
Out
Secondary discharge
V8
Out
Triggered system
V9
Out
General trouble
V10
Out
General disable
Parts of the H-S81-HS System
applicable up to SIL3
Yes
250mA
No
22-29VDC
10mA
-5 - 50 °C
-30 - 80 °C
95% (RH) non-condensing
yes
69