Configuration; Field Connections - Honeywell H-S81-HS Operation Manual

Industrial fire panel
Hide thumbs Also See for H-S81-HS:
Table of Contents

Advertisement

I/O modules

Configuration

By using the configuration program ProS81, the following parameters can be set for each output
channel:
Function
Operating mode
Timing
Output type
Output status in case of CPU fault
Enable/Disable status export to Hosts
Enable/Disable commands from Hosts on
the channel

Field Connections

The module can be connected to field terminal block by using a flat or a multi-conductor cable,
depending on the used bus type.
S81-E2001-1 Bus
Thanks to this bus, the module can be terminated by using a S81-T8001-1 termination module with
16 terminals or a S81-T8007-2 16-relay module.
S81-T8007-2
When this termination type is used, there will be sixteen relay outputs with one 4A SPDT contact to
be used exclusively for connecting circuits operating with SELV voltage.
S81-E2001-2 Bus
Thanks to this bus, the module can be terminated by using a S81-CCT1 16-conductor multi-polar
cable or a S81-T8007-2 16-relay module.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Mode
Continuous-Normally Energized, Continuous-Normally de-energized, Intermittent,
Pulsing-1, Pulsing-2, ISA-1A Alarm Sequence, Delayed on activation, Delayed on
enabling, Delayed on deactivation
1 to 255 seconds/minutes (only for pulsing and intermittent modes)
Normal / Sounder
Frozen in the last status / Off
No, TCP1, TCP2, RS232
No, TCP1, TCP2, RS232
Parts of the H-S81-HS System