Internal Connections; 3: Pu-A0004-1 Battery Charger Module - Honeywell H-S81-HS Operation Manual

Industrial fire panel
Hide thumbs Also See for H-S81-HS:
Table of Contents

Advertisement

Power Supply Set

Internal Connections

WARNING: HIGH VOLTAGE
!
THIS MODULE INCLUDES CIRCUITS WITH VOLTAGE AND CURRENT VALUES POTENTIALLY
DANGEROUS FOR PEOPLE.
2.1.3 PU-A0004-1 Battery Charger Module
This is a UPS able to control and charge two 12 Volt batteries with a maximum
capacity of 65Ah. Battery maximum charge current can be set through a dip-
switch on the module. Under normal operating conditions, a simplified test is
carried out every 30 seconds in order to check the proper presence of the batter-
ies. A full test, instead, is carried out every hour in order to check electrical con-
nections and battery efficiency. During battery trickle charge, battery voltage is
compensated automatically according to the temperature. In case of mains volt-
age failure, batteries are automatically switched to the load without any interrup-
tions. Should the full charge stage exceed 24 hours, the power supply unit will
signal a battery fault. In case of primary power supply failure, the system will
shut batteries down when the on-load voltage is lower than 18VDC in order to
avoid damaging the batteries. The set features three open collector outputs for
replicating the faults to the alarm control panel, two inputs for monitoring the
power supply units and one RS232 port for the connection to a supervisory sys-
tem. It can be used together with one or more PU-A0005-1 power supply units.
In this case, the resulting power supply set will be fully compliant with the
EN54-4:1997/A2:2006 standard.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
INPUT POWER SUPPLY CONNECTIONS
Tag.
Terminal
Name
M1
L input
TB1
M2
N input
M3
PE
CURRENT SHARE AND STATUS REPLICATION CONNECTIONS
Tag.
Terminal
Name
M1
RL-COM1
M2
RL-NO1
TB2
M3
RL-COM2
M4
RL-NO2
M5
SHARE (+)
OUTPUT POWER SUPPLY CONNECTIONS
Tag.
Terminal
Name
M1
- V. OUT
M2
- V. OUT
TB3
M3
+V. OUT
M4
+V. OUT
Parts of the H-S81-HS System
Function
Phase (protected by internal fuse)
Neutral
Earth
Function
Status relay 1 common
Status relay 1 NO
Status relay 2 common
Status relay 2 NO
Signal for load distribution
Function
Output voltage negative
Output voltage negative
Output voltage positive
Output voltage positive
29