4: Standard Options - Honeywell H-S81-HS Operation Manual

Industrial fire panel
Hide thumbs Also See for H-S81-HS:
Table of Contents

Advertisement

Configuration
7.10.4 Standard Options
This option allows to display standard configuration parameters as shown in the picture below. In
order to change the parameters use the Arrow and Number keys and confirm by pressing Enter.
Press Esc to exit and go back to the previous menu.
International Standard This parameter can be changed from the operator cycle and indicates the
Number of CPUs
Calibration Time
LCD Backlight
• On:
• Off:
• Timed:
Audible indication
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Figure 7.22 Standard Options
international standard used by the control panel. It can be: EN for control panels
intended for the European market, or UL864 for the control panels for the US
market.
It defines the number of CPUs installed in the control panel (1-2)
This parameter sets the calibration time of analog smoke detectors. The default
setting is 4.00 am.
This parameter sets the operating mode of display backlighting.
Display backlight always on;
Display backlight always off;
Display backlight switches off automatically after an idle time of one minute. (default
setting)
It defines the operating mode of the internal sounder. By selecting the Fire Sounder
Mode the internal sounder is activated in case of fire alarm or further to the
evacuation command. By selecting the Buzzer Mode the sounder is activated
simultaneously to the local Buzzer.
Operating Instructions
145