Layout of H-S81-HS/1-10R Internal Parts

3.7 Layout of H-S81-HS/1-10R Internal Parts
The picture below shows the typical layout of the parts located on the base plate of the H-S81-
HS/1-10R type control panels. In this specific configuration, field device cables can be connected
to I/O modules either with TB terminal blocks or with M termination modules. This kind of config-
uration allows to install both the PU-0001 power supply set on the base plate and the PU-0002
power supply set on the rack. The cable conduits colored in black are for AC primary supply cables
only and must not be used for laying other cables.

3.8 Cable Entry

For cable entry use the proper plates located on the steelwork bottom and already drilled to house
cable connectors. For the entry of the main supply cable, use the proper cable connector on the right
side of the pre-drilled plate.
NOTE:
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Figure 3.6 H-S81-HS/1-10R Internal Plate
Use only cable connectors with V1 or higher flammability rating.