Termination modules

Standard Connection Diagrams

Figure 2.48 – Inputs and Local Sounder Output Standard Connection Diagram
2.5.6 S81-T8006-1

Technical Features

• Supply voltage:
• Quiescent current:
• Contact type:
• Contact capacity:
• Assembly:
• Operating temperature:
• Storage temperature:
• Maximum humidity:
• Dimensions:

Status Indications

The module includes 8 green LEDs for relay status indication:
LED1 - LED8 (Green LEDs)
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
22-29VDC
0mA
SPDT
4 A 30VDC
on DIN bar
-5 - 50 °C
-30 - 80 °C
95% (RH) non-condensing
W 135 x H 77 x D 50 mm
LED
Condition
It lights up when relay coil is active
Parts of the H-S81-HS System

Description

It is used with S81-E2001-1 type
buses to terminate S81-F5001-1 mod-
ules. It features 8 x SPDT output con-
tacts to connect SELV circuits only.