Parts of the H-S81-HS System
Function
Output 1
-
Output 2
-
Output 3
-
Output 4
-
Output 5
-
Output 6
-
Output 7
-
Output 8
-
Output 9
-
Output 10
-
Output 11
-
Output 12
-
Output 13
-
Output 14
-
Output 15
-
Output 16
-
Common Positive
+
2.4.7 S81-F5003-1
64
H-S81-HS Installation & Operation Manual — Form Number XX-XXXX—X P/N LS10114-000HI-E:A 2/24/2015
Termination with Flat Cable
1
2
3
4
5
6
7
8
9
10
11
12
S81-T8001-1
13
14
15
16
Figure 2.29 Field Connections

Description

Module with 8 x 250 mA monitored output channels for sounder control. Outputs
are controlled by two virtual channels for allowing both continuous and intermit-
tent output control. Line is monitored by polarity reversal.

Technical Features

• Redundancy:
• Channel test:
• Max. output current
• Automatic output protection:
• Supply voltage:
• Quiescent current:
• Operating temperature:
• Storage temperature:
• Maximum humidity:
• Hot swap capability:

Status Indications

Each one of the eight channels on the front panel includes two status LEDs.
Output channel status
Off
Disabled
Trouble
Active
Key to symbols ⊗= steady on LED; − = LED off; ∅= flashing LED
Termination with Multi-conductor Cable
White
1
Brown
2
Green
3
Yellow
4
Gray
5
Pink
6
Blue
7
Red
8
Black
Violet
Gray/Pink
Red/Blue
White/Green
Brown/Green
White/Yellow
Yellow/Brown
White/Gray
No
No
250mA
Yes
22-29VDC
38mA
-5 - 50 °C
-30 - 80 °C
95% (RH) non-condensing
yes
Indications 1 - 8 Out LEDs
Yellow LED
I/O modules
S81/CCT1
RED LED

Hide quick links: