Standard Connection Diagrams; 6: S81-F5002-1; Description; Technical Features - Honeywell H-S81-HS Operation Manual

Industrial fire panel
Hide thumbs Also See for H-S81-HS:
Table of Contents

Advertisement

Parts of the H-S81-HS System

Standard Connection Diagrams

NOTE: The module can control resistive or inductive loads with a maximum current of 500mA. If
the module is used for controlling filament lamps, the maximum load power cannot exceed 4W.
2.4.6 S81-F5002-1
62
Figure 2.28 Standard Connection Diagram

Description

Module with sixteen non monitored 250mA open collector outputs. It is also
used together with the S81-T8007-2 16-relay module.

Technical Features

• Redundancy:
• Channel test:
• Max. output current
• Automatic output protection
• Supply voltage:
• Quiescent current:
• Operating temperature:
• Storage temperature:
• Maximum humidity:
• Hot swap capability:

Status Indications

Each one of the sixteen channels on the front panel includes a status LED.
Output Channel Status
Channel under normal condition
Enabled channel
⊗= steady on LED;
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
No
No
250mA
No
22-29VDC
10mA
-5 - 50 °C
-30 - 80 °C
95% (RH) non-condensing
yes
− = LED off
I/O modules
Indications 1-16
Out LEDs