Central Unit Rack
Technical features
• Supply voltage:
• Quiescent current:
• Operating temperature:
• Storage temperature:
• Maximum humidity:
• LCD resolution:
• Backlighting:
• Hot swap capability:
Status Indications
The front panel includes 14 LEDs with the following functions:
Module rear panel includes 5 LEDs with the following functions:
LED
LD15 (Yellow)
LD16 (Yellow)
CPU-A Link (Green)
CPU-B Link (Green)
S81-T8004-1 Link
Buttons
Button
Description of buttons
Local Buzzer Silencing
System sounder silencing
Control panel reset
Evacuation command
Delay time reset
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
22-29VDC
70mA
-5 - 50 °C
-30 - 80 °C
95% (RH) non-condensing
320 x 128 pixels
LED
yes
LED
Alarm (Red)
General Trouble (Yellow)
Device Trouble (Yellow)
Sounder Trouble (Yellow)
PSU1 Trouble (Yellow)
PSU2 Trouble (Yellow)
Ground Fault (Yellow)
System Trouble (Yellow)
Zone Testing (Yellow)
General disable (Yellow)
Device disable (Yellow)
Sounder disable (Yellow)
Output Delay (Yellow)
Voltage detection (Green)
∅ = flashing ⊗ = steady on
Indication
Currently not used
Currently not used
Steady on when the communication Link with CPU-A is present
Steady on when the communication Link with CPU-B is present
Steady on when the communication Link with S81-T8004-1 is present
Level
1-2-3
Deactivates the local buzzer
2-3
Silencing of system fire alarm sounders
2-3
Resets the control panel
2-3
Activates system fire alarm sounders
1-2-3
Cancels output delay timer
Mode
Indication
∅
Non acknowledged alarm condition
⊗
Acknowledged alarm condition
∅
General trouble condition
∅
Sensors/actuators trouble
∅
Alarm sounder trouble
∅
Primary power supply trouble
∅
Secondary power supply trouble
∅
Earth leakage
∅
System trouble
∅
Ongoing zone test
⊗
General disable condition
⊗
Disabled sensors/actuators
⊗
Disabled alarm sounder
⊗
Activation delay timer on
⊗
Primary voltage detection
Description of the function
Parts of the H-S81-HS System
41