Safety and Availability of the H-S81-HS System

1.3.6 Electromagnetic Compatibility (CE)
The H-S81-HS system has been designed and tested for resisting to standard levels of radiated and
conducted electromagnetic interference, and electrostatic discharges. The table below lists the types
and levels of the tests undergone by the H-S81-HS system.
Basic Standard
Date Title
EN 61000-4-2
1995
A1
1998
A2
2001
EN 61000-4-3
1996
A1
1998
A2
2001
EN 61000-4-4
1995
A1
2001
A2
2001
EN 61000-4-5
1995
A1
2001
ENV 50141
1994 Conducted disturbances induced by radio-
EN 61000-4-11
1994
A1
2001
CAUTION:
!
ELECTRICAL DISTURBANCES VARY SIGNIFICANTLY ACCORDING TO THE TYPE OF
INSTALLATION AND WIRING DISTANCE TO AND FROM OTHER DEVICES. THEREFORE, IT IS
IMPORTANT TO MAKE SURE THAT THE ELECTROMAGNETIC INTERFERENCE LEVELS DO
NOT EXCEED THE VALUES REPORTED IN THIS TABLE.
1.4 Safety and Availability of the H-S81-HS System
The H-S81-HS system is intended for use in applications requiring a high safety level, together
with high system availability. According to the required safety and availability levels, different
H-S81-HS system configurations can be provided.
1.4.1 Possible Configurations of the H-S81-HS System

"Mono" Configuration

This solution includes the duplicated central unit and the I/O modules in a single configuration.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Electrostatic discharge immunity test
Radiated, radio-frequency, electromagnetic
field immunity test
Electrical fast transients/bursts immunity test
Surge immunity test
frequency fields immunity test
Voltage dips, short interruptions and voltage
variations immunity test
ELECTROMAGNETIC COMPATIBILITY
Figure 1.3 "Mono" Configuration
General Description
Noise Immunity Tests
6 kV contact discharge
8 kV air discharge
10 V/m, 80 MHz-2 GHz, 80% AM
2 kV power supply
1 kV signal lines
2 kV common mode
1 kV differential mode
10 V, 150 kHz-80 MHz, AM
60% 200ms
100% 100ms
19