Possible Configurations; 5: Pu-A0007-1 Drawer With Slots; Description - Honeywell H-S81-HS Operation Manual

Industrial fire panel
Hide thumbs Also See for H-S81-HS:
Table of Contents

Advertisement

Power Supply Set

Possible Configurations

Features
Number of PU-A0008-1 power supply units
Power supply voltage
Rated frequency
Max. input current at 110V~
Max. input current at 240V~
Nominal output voltage
Max. residual ripple
Minimum output voltage
Min. output current
Max. output current
Maximum battery resistance
Max. battery current
Maximum battery capacity
1 Full load output voltage with low batteries in case of mains voltage failure
2 Current for the loads plus the current required by the control panel
3 Internal resistance of batteries and relevant circuits. (Cables, terminals, fuses, etc.)
2.1.5 PU-A0007-1 Drawer with Slots

Description

It is a 19 inch rack that can contain a PU-A0009-1 battery charger module and up to four
PU-A0008-1 power supply modules. It features ventilation, consisting in three fans with a diameter
of 120 mm. The terminal blocks for power supply and status replication connection are located on
slot back.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
1
2
2
3
Figure 2.4 S81-PU002 Power Supply Set Slot
Parts of the H-S81-HS System
S81-PU002-2
S81-PU002-4
2
110-240V~
50-60Hz
6A
2.7A
25VDC ±2%
<115mV
18.9VDC
8A duplicated
20A duplicated
12A duplicated
32A duplicated
0.1 Ω
6A
2x12V 120Ah
2x12V 120Ah
4
110-240V~
50-60Hz
12A
5.25A
25VDC ±2%
<115mV
18.9VDC
0.05 Ω
6A
33

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents