Operator Interface
PSU1 TROUBLE LED (burglar/fire alarm function)
It flashes in case of primary power supply fault. It goes out automatically when the cause is solved.
PSU2 TROUBLE LED (burglar/fire alarm function)
It flashes in case of secondary power supply fault. It goes out automatically when the cause is
solved.
GROUND FAULT (LEAKAGE TROUBLE) LED (burglar/fire alarm function)
It flashes in case of voltage leakage to ground. It goes out automatically when the cause is solved.
SYSTEM TROUBLE LED (burglar/fire alarm function)
It flashes in case of system fault. It goes out automatically when the cause is solved.
ONGOING ZONE TEST LED (fire alarm function)
It flashes when a zone is set to test mode. It goes out automatically when the test is completed.
GENERAL DISABLE LED (fire alarm function)
It is steady on in case of any disable relating to area 1 (Safety).
DEVICE DISABLE LED (fire alarm function)
It is steady on in case of sensor or actuator (other than sounders) disable in area 1.
SOUNDER DISABLE LED (fire alarm function)
It is steady on in case of disable of an actuator defined as sounder in area 1.
OUTPUT DELAY LED (fire alarm function)
It flashes during the delay time count for the activation of one area 1 actuator. It goes out automati-
cally when this count is over or when the delay override button is pressed.
AC POWER LED (burglar/fire alarm function)
It is steady on when primary supply voltage is detected (PSU1). It goes out in case of primary sup-
ply voltage failure.
The back of the module includes three LEDs with the following functions:
Green LED: CPU-A Link
Steady on in presence of communication link to CPU-0.
Green LED: CPU-B Link
Steady on in presence of communication link to CPU-1.
Green LED: T8004-1 Link
Steady on in presence of communication link to default I/O module.

7.1.2 Buttons

Local Buzzer Silencing (fire alarm function)
It operates at access level 1 or higher, and switches off only the local buzzer relating to fire
alarm functions. The display shows a message informing that the buzzer has been silenced, which
is stored in the event history and sent to any peripheral devices (host/printer).
Control Panel Reset (fire alarm function)
At access level 2 or higher, it resets all currently active control panel alarms or troubles in
area 1. The display shows a message informing that reset has been completed, which is stored in the
event history and sent to any peripheral devices (host/printer). This function can be activated only
after silencing local buzzer and sounders.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Operating Instructions
129