2.4.1 S81-F3002-1 & S81-F3002-2

Status Indications

Each one of the eight channels on the front panel includes two status LEDs providing the following
information:
Indications Line LEDs 1-8 in SAFETY mode
Input channel status
Normal
Disabled
Trouble
Tampering
Pre-alarm
Alarm
Key to symbols: ⊗= steady on LED; − = LED off, ∅= flashing LED, −−−= function not available
46
Module with 8 x 500mA monitored outputs for solenoids
Module with 8 x 500mA monitored outputs for solenoids
Module with 16 x 250mA non monitored outputs
Module with 8 x 250mA monitored outputs for sounders
Module with 4 x 2A monitored outputs for solenoids
Module with 4 x 2A monitored outputs for solenoids
Module with 8 outputs for fire extinguishing system control
Logic module
Loop control module with ESP protocol
Modbus RTU Master/Slave module
Loop control module with SSP protocol
Control modules for weighing modules
Loop control module with XP95/Discovery protocol
Loop control module with System Sensor protocol

Description

Eight balanced input module for conventional safety related sensors. All chan-
nels can be reset individually and are tested every 30 seconds during operation.
This module is suitable for controlling detection systems with conventional
lines and can be used in systems with already existing detection lines for con-
trolling automatic fire extinguishing systems with double enable logic or intrin-
sically safe systems. It is also used for controlling all the devices typical of fire
extinguishing systems (pressure switches, discharge buttons, etc.). This module
can be duplicated in fault tolerant systems; in this case, the two modules shall
be placed on adjacent racks in the same position. In this configuration, the eight
detection lines are connected to both modules.

Technical Features

• Safety rating:
• Redundancy:
• Alarm threshold:
• Line short circuit current
• Channel test:
• Intrinsic Safety Barriers allowed:
• Supply voltage:
• Quiescent current:
• Operating temperature:
• Storage temperature:
• Maximum humidity:
• Hot swap capability:
Yellow LED
Red LED
−−−
−−−
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Redundancy not possible
Redundancy possible
Redundancy not possible
Redundancy not possible
Redundancy not possible
Redundancy possible
Redundancy not possible
Redundancy not possible
Redundancy not possible
Redundancy not possible
Redundancy not possible
Redundancy not possible
Redundancy not possible
Redundancy not possible
applicable up to SIL3
S81-F3002-2 model
2 programmable thresholds on 255 levels
>115mA
every 30 seconds
uZ680+ Pepperl & Fuchs
22-29VDC
14mA
-5 - 50 °C
-30 - 80 °C
95% (RH) non-condensing
yes
Indications Line LEDs 1-8 in SECURITY mode