Serial Interface A-B
The following figure shows the connections of the serial interface and the position of the
micro-switch for the bus termination resistor.

Connection Terminals of the Serial Interface and Microswitch S4

(Bus Terminating Resistor)

The two control signal terminals A and B enable the connection of a shielded RS485
twisted-pair cable.
The bus terminating resistor required at the end of a data cable is integrated in the frequency
inverter and can be connected via microswitch S4.
The network cable must have a bus termination resistor (120 ohms) connected at each
physical end to prevent reflections and the resulting transmission faults.

Two-Wire RS485 Connection

(Slave = M-Max Frequency Inverter)
120 ohms
Slave
S4
A
B
RS485
Modbus (RTU)
The parameter definition of the serial interface is described in "Serial Interface
(Modbus RTU)" on Page 131.