Fixed Frequency Setpoint Value

Access
PNU
ID
RUN
P10.1
124
P10.2
105
P10.3
106
P10.4
126
P10.5
127
P10.6
128
P10.7
129
P10.8
130
Value/Range
Description
Fixed frequency FF0
0.00–P6.4
0.00 Hz up to the maximum frequency value (P6.4)
This value is only active if the setpoint input has been set to
parameter P6.2 = 0
Fixed frequency FF1
0.00–P6.4
0.00 Hz up to the maximum frequency value (P6.4)
In the factory setting, this value can be called directly via DI3
(control signal terminal 10)
Fixed frequency FF2
0.00–P6.4
0.00 Hz up to the maximum frequency value (P6.4)
In the factory setting, this value can be called directly via DI4
(control signal terminal 14)
Fixed frequency FF3
0.00–P6.4
0.00 Hz up to the maximum frequency value (P6.4)
In the factory setting, this value can be called directly by joint
actuation of control signal terminals 10 and 14 (DI3 and DI4)
Fixed frequency FF4
0.00–P6.4
0.00 Hz up to the maximum frequency value (P6.4)
For activation, parameter P3.11 must be assigned a third digital
input. For example, P3.11 = 5: DI5 (control signal terminal 15)
This value can then be called up directly via DI3
Note: In the factory setting, DI5 (control signal terminal 15) is
assigned with the error acknowledgement (Reset). Setting
P3.11 = 0 is recommended
Fixed frequency FF5
0.00–P6.4
0.00 Hz up to the maximum frequency value (P6.4)
For activation, parameter P3.11 must be assigned a third digital
input. For example, P3.11 = 5: DI5 (control signal terminal 15),
see Note on P10.5)
This value can be called directly by joint actuation of control
signal terminals 10 (DI3) and 15 (DI5)
Fixed frequency FF6
0.00–P6.4
0.00 Hz up to the maximum frequency value (P6.4)
For activation, parameter P3.11 must be assigned a third digital
input. For example, P3.11 = 5: DI5 (control signal terminal 15)
see Note on P10.5)
This value can be called directly by joint actuation of control
signal terminals 14 (DI4) and 15 (DI5)
Fixed frequency FF7
0.00–P6.4
0.00 Hz up to the maximum frequency value (P6.4)
For activation, parameter P3.11 must be assigned a third digital
input. For example, P3.11 = 5: DI5 (control signal terminal 15),
see Note on P10.5)
This value can be called directly by joint actuation of control
signal terminals 10 (DI3), 14 (DI4) and 15 (DI5)
M-Max Series Adjustable Frequency Drive MN04020003E—October 2013 www.eaton.com
Parameters
Factory Setting
(P1.3)
6.00
12.00
18.00
24.00
30.00
36.00
48.00
60.00
101