V/Hz-Characteristic Curve, continued
Access
PNU
ID
RUN
P11.9
601
X
P11.10
522
X
Value/Range
Description
Carrier frequency
1.5–16.0 kHz
Using a high switching frequency can reduce the magnetization
noise in the motor
The heat dissipation in the inverter (IGBT) increases with higher
switching frequencies
With motor frequencies <5 Hz a higher speed stability can be
achieved at low switching frequencies
Note: As a protection against thermal overload, MMX reduces
the switching frequency automatically if, for example, too high
values are set and with high ambient temperatures and high
load currents
Parameter P11.10 = 1 must be set for operation at a constant
carrier frequency
Sine-wave filter (constant carrier frequency)
0
Deactivated
1
Enabled
Note: When using a sinusoidal filter, the carrier frequency must
be constant