Default I/O

Designation
Terminal
Function
DI1
8
Start Fwd
DI2
9
Stop/Start Rev
DI3
10
Fixed Frequency B0 (12 Hz)
DI4
14
Fixed Frequency B1 (18 Hz)
DI5
15
Fault Reset
Parameter Selection (P1)
In the parameter selection (P1), you can choose between the
factory set quick configuration (P1.1 = 1) with a reduced
parameter set and all parameters (P1.1 = 0).
The setting of the parameters with the quick configuration
(P1.1 = 1) is guided by a Quickstart Wizard. (A listing of
parameters is on Page 66.) Each executed parameter must
be processed in succession up to frequency display M1.1.

Parameter Selections

Access
PNU
ID
RUN
P1.1
115
P1.2
540
X
P1.3
1472
X
Parameter
P3.1, P3.2
P3.1, P3.3
P3.9, P10.2
P3.10. P10.3
P3.7
Value/
Range
Description
Quick start parameters
0
All parameters
All parameters are shown and can be changed. Exit from Quickstart.
1
Only quick configuration parameters
Only the selected parameters of the quick configuration are shown and can
be changed (see Page 66 for list of parameters)
Application
(See listing of the predefined application parameters in the table on
Page 66)
0
Basic
1
Pump drive
2
Fan drive
3
High load (for example, hoisting or conveyor)
Country specific default settings
0
EU (Europe, 50 Hz networks)
1
NA (North America, 60 Hz networks)
The country specific factory setting takes into account the frequency
based parameters in relation to 50 and 60 Hz networks:
PNU
Designation
P6.4
Maximum frequency
P7.3
Motor, rated speed
P7.6
Motor, rated frequency
P11.2
Cut-off frequency
P11.4
V/Hz characteristic curve, mean
frequency value
P14.3
Motor (2PS) nominal speed
P14.6
Motor (2PS) nominal frequency
P14.8
Maximum frequency (2PS)
M-Max Series Adjustable Frequency Drive MN04020003E—October 2013 www.eaton.com
Designation
Terminal
Function
DI6
16
PID Controller Deactivate
RO1 (NO)
22/23
Run
RO2 (NO/NC)
24/25/26
Fault
DO
13
Ready
A return to a previous parameter is not possible here. The
preset application parameters are selected under P1.2.
Only when the quick start assistant (M1.1) is completed can
the parameters be called again and then also individually.
With P1.1 = 0 (all parameters) and P1.2 = 0, 1, 2, or 3, you
can link the predefined application values with all
parameters.
Every single parameter value is reset to factory settings
every time that the application menu is activated.
P1.3 = 0
50 Hz
1440 RPM
50 Hz
50 Hz
25 Hz
1440 RPM
50 Hz
50 Hz
Parameters
Parameter
P3.12
P5.1, P5.10
P5.2, P5.11
P5.3, P5.9
Factory Setting
(P1.3)
1
0
1
P1.3 = 1
60 Hz
1720 RPM
60 Hz
60 Hz
30 Hz
1720 RPM
60 Hz
60 Hz
67