Determining The Program Number (P10.10) - Eaton M-Max Series User Manual

Adjustable frequency drive
Hide thumbs Also See for M-Max Series:
Table of Contents

Advertisement

Parameters
Sequence Control
The sequence control enables a cyclical program sequence with the fixed frequency setpoints
FF0 to FF7. To run the program you can also select from four different operating modes and
assign rotation direction (FWD/REV) and run time to the individual fixed frequencies. The
program sequence is programmed in binary code and is represented by a decimal number for
simple entry.
Fixed Frequency Setpoint Value, continued
Access
PNU
ID
RUN
P10.9
1436
P10.10
1437
The table below shows the parameters of the fixed frequencies (P10.1–P10.8) with the
associated run times (P10.11–P10.18) and the corresponding values in binary and decimal
format.
Depending on the selected rotating field direction (FWD/REV), the decimal value is multiplied
by 0 (= FWD) or 1 (= REV). The sum of all decimal values forms the program number for
parameter P10.10.

Determining the Program Number (P10.10)

Fixed Frequency
Hz
s
FF0
P10.1
P10.11
FF1
P10.2
P10.12
FF2
P10.3
P10.13
FF3
P10.4
P10.14
FF4
P10.5
P10.15
FF5
P10.6
P10.16
FF6
P10.7
P10.17
FF7
P10.8
P10.18
The fixed frequencies (FF0–FF7) are only active if the run times (P10.11–P10.18) of the
associated parameters are set (>0s).
102
M-Max Series Adjustable Frequency Drive MN04020003E—October 2013 www.eaton.com
Value/Range
Description
PLC Sequence control, operating mode
Selection of operating modes for cyclical program execution
The start of the program execution via a digital input (DI1–DI6)
is executed according to parameter P3.21
The pause of the program execution via a digital input (DI1–DI6)
is executed according to parameter P3.22
0
Deactivated
1
Execute program cycle once
2
Execute program cycle continuously
3
Execute program cycle in steps
4
Execute program cycle continuously in steps
PLC Sequence control, program (FWD/REV)
0–255
Summated decimal value from the binary coded program
sequence (see table below)
Values
Binary
Decimal
0
2
1
1
2
2
2
2
4
3
2
8
4
2
16
5
2
32
6
2
64
7
2
128
Sequence control, program (FWD/REV): P10.10 =
Example A
(See Figure on
FWD
REV
Page 104)
0
1
FWD
0
1
FWD
0
1
FWD
0
1
FWD
0
1
FWD
0
1
FWD
0
1
FWD
0
1
FWD
Factory Setting
(P1.3)
0
0
Example B
(See Figure on
Page 105)
0
FWD
0
0
FWD
0
0
FWD
0
0
FWD
0
0
FWD
0
0
FWD
0
0
REV
64
0
REV
128
0
192