Digital Outputs (P5)
The M-Max series frequency inverters have three digital
outputs in different specifications:
Relay RO1: N/O contact R13–R14, control signal terminals
22 and 23
Relay RO2: changeover contact R21–R22 (N/C contact,
control signal terminals 25 and 24)/R21–R24 (N/O contact,
control signal terminals 25 and 26)
Transistor output DO: control signal terminal 13 (DO–).
Control signal terminal 20 (DO+) = Input of the supply
voltage for the transistor output
Notes on electrical connections are found on Pages 44
and 45.
The messages listed under parameter P5.1 can be assigned
multiple times. These are independent of the selected
control level and operating mode.

Digital Outputs

Access
PNU
ID
RUN
P5.1
313
78
M-Max Series Adjustable Frequency Drive MN04020003E—October 2013 www.eaton.com
Value/Range
Description
RO1 Signal (Relay 1 Output)
0
Deactivated
1
READY, the frequency inverter is ready for operation
2
RUN, the inverter of the frequency inverter is enabled
(FWD, REV)
3
FAULT, error message
Error detected (= STOP)
4
Error message inverted (no error message)
5
ALARM, warning message
See "Protective Functions (P8)" on Page 90
6
REV (Reverse run), anticlockwise rotating field active
7
Output frequency = frequency setpoint (at speed)
8
Motor controller active
9
Zero frequency
Output frequency = 0 Hz
10
Frequency monitoring 1
For the frequency ranges set at P5.4 and P5.5
11
Frequency monitoring 2
For the frequency ranges set at P5.6 and P5.7
12
PID monitoring
For the deviation set at P9.17
Values continued on next page

Digital Outputs

22
23
25
24
26
13
20
Factory Setting
(P1.3)
2