Drives Control, continued
Access
PNU
ID
RUN
P6.24
509
X
P6.25
510
X
P6.26
511
X
P6.27
512
X
P6.28
513
X
P6.29
514
X
Setting Range for Skip Frequencies
f
Hz
t
P6.30
759
X
P6.31
1481
X
P6.32
1482
X
P6.33
1483
X
Notes
: P6.24, P6.26, P6.28
: P6.25, P6.27, P6.29
In systems with mechanical resonances, you can cut out these frequency ranges for stationary operation.
Up to three different frequency ranges can be set.
Value/Range
Description
Skip frequency 1, lower value
0.00–P6.25 Hz
Skip frequency 1, upper value
P6.24–P6.4
Skip frequency 2, lower value
0.00–P6.27 Hz
Skip frequency 2, upper value
P6.26–P6.4 Hz
Skip frequency 3, lower value
0.00–P6.29 Hz
Skip frequency 3, upper value
P6.28–P6.4 Hz
Automatic REAF attempts
1–10
Define the permissible number of automatic restarts
(REAF = Restart After Failure)
Manual mode, primary control source
Like P6.1
Assignment of the control levels
Manual mode is activated via parameter P3.37
Manual mode, primary speed reference
Like P6.2
Assignment of setpoint sources
Manual mode is activated via parameter P3.37
Manual mode, KEYPAD lock
The Start/Stop functions are blocked in Manual mode via the
keypad
0
Deactivated
1
Enabled
M-Max Series Adjustable Frequency Drive MN04020003E—October 2013 www.eaton.com
Parameters
Factory Setting
(P1.3)
0.00
0.00
0.00
0.00
0.00
0.00
3
1
3
1
87