Second Parameter Set (P14)
The selected parameters for a second motor are combined in
parameter group P14. This enables the alternative operation
of two motors at the output of the frequency inverter, even
with different rating specifications.
In the factory setting, the parameters of this second
parameter set (P14) are identical to the factory settings of
the basic parameters (first parameter set) and described in
the relevant sections:
Second Parameter Set
Access
PNU
ID
RUN
P14.1
1347
X
P14.2
1352
X
P14.3
1350
X
P14.4
1351
X
P14.5
1348
X
P14.6
1349
X
P14.7
1343
X
P14.8
1344
X
P14.9
1345
P14.10
1346
Note
Default values vary based on actual unit ratings.
Value/Range
Description
—
Motor rated current (2PS)
0.2 x I e –2 x I e
Ie = Rated operational current of the frequency inverter
(See motor rating plate)
—
Current limit (2PS)
0.2 x I e –2 x I e
1.5 x I e
—
Motor rated speed (2PS)
300–20,000 RPM (See motor nameplate)
—
Motor power factor (cos
0.30–1.00
(See motor nameplate)
—
Motor rated operating voltage (2PS)
180–676V
(See motor nameplate)
Pay attention to the supply voltage and the type of circuit
in the stator winding
—
Motor nominal frequency (2PS)
30–320 Hz
(See motor rating plate)
—
Minimum frequency (2PS)
0.00–P14.8 Hz
—
—
Maximum frequency (2PS)
P14.7–320 Hz
—
—
Acceleration time (2PS) (acc3)
0.1–3000s
—
—
Deceleration time (2PS) (dec3)
0.1–3000s
—
M-Max Series Adjustable Frequency Drive MN04020003E—October 2013 www.eaton.com
P14.1–P14.6 = P7.1–P7.6 (motor)
●
P14.7–P14.10 = P6.3–P6.6 (drives control)
●
P14.11 = P11.1, P14.12 = P11.7 (V/f control)
●
P14.13–P14.16 = P8.6–P8.9 (protection function)
●
) (2PS)
Parameters
Factory Setting
(P1.3)
I e
1.5 x I e
60.00
0.00
60.00
3.0
3.0
121