Logic Linking Of A And B - Eaton M-Max Series User Manual

Adjustable frequency drive
Hide thumbs Also See for M-Max Series:
Table of Contents

Advertisement

Parameters
Logic Function (P13)
The logic function enables you to link both parameters P13.1 (A) and P13.2 (B) logically with
each other. The result (LOG) can then be assigned to the digital outputs DO (P5.3), RO1 (P5.1)
and RO2 (P5.2). The type of operation (And, Or, Exclusive-Or) is defined in parameter P13.3.

Logic Linking of A and B

P13.1
0
A
1
...
28
P13.2
0
1
B
...
28
Example: Digital output RO1 (N/O contact R13/R14) is required to indicate during operation
that the set current limit has been reached:
P5.1 = 24, LOG function fulfilled
P13.1 = 2, Operation (RUN), signal A
P13.2 =27, Current monitoring, signal B
P13.3 = 0, A AND B
118
M-Max Series Adjustable Frequency Drive MN04020003E—October 2013 www.eaton.com
P13.3
A AND B
0
A OR B
1
LOG
A XOR B
2
DO1
24
P5.3
RO1
24
P5.1
RO2
24
P5.2
DO+
20
DO–
13
R13
22
R14
23
R21
25
R22
24
R24
26

Hide quick links: