Motor
Access
PNU
ID
RUN
P7.1
113
X
P7.2
107
X
P7.3
112
X
P7.4
120
X
P7.5
110
X
P7.6
111
X
Note
Default values vary based on actual unit ratings.
Value/Range
Description
—
Motor, rated operational current
0.2 x I e –2 x I e (A)
I e = Frequency inverter's rated operational current
(See figure on Page 88.)
—
Current limit
0.2 x I e –2 x I e (A)
Factory setting: 1.5 x I e
—
Motor, rated speed
300–20000 RPM
(See figure on Page 88.)
–1
(min
)
—
Motor, power factor (cos
0.30–1.00
(See figure on Page 88.)
—
Motor, rated operating voltage
180–676V
(See figure on Page 88.)
Pay attention to the supply voltage and the type of
circuit in the stator winding
—
Motor, rated frequency
30–320 Hz
(See figure on Page 88.)
M-Max Series Adjustable Frequency Drive MN04020003E—October 2013 www.eaton.com
Factory Setting
(P1.3)
I e
1.5 x I e
1720
)
0.85
60.00
Parameters
89