Mechanical Brake (Actuation)
The actuation of an external mechanical brake can be
implemented via one of the digital outputs (see "Digital
Outputs (P5)" on Page 78), if the value 26 (= External brake
actuated) is assigned:
Transistor output DO: control signal terminal 20 (DO–),
●
supply voltage control signal terminal 13 (DO+), maximum
48 Vdc/50 mA, Parameter 5.3
Relay RO1: N/O contact control signal terminal 22 (R13)
●
and 23 (R14), maximum 250 Vac/2A or 250 Vdc/0.4A,
Parameter P5.1
Relay RO2: changeover contact, control signal terminal
●
25 (R21), 24 (R22) and 26 (R24), maximum 250 Vac/2A or
250 Vdc/0.4A, Parameter P5.2
Braking, continued
Access
PNU
ID
RUN
P12.7
1448
X
P12.8
1449
X
P12.9
1450
X
P12.10
1451
X
P12.11
1452
X
Value/Range
Description
—
External brake, delay time opening
0.00–320.00s
Condition: RUN (Start enable)
After the time set here has elapsed, the brake is actuated
(P5._ is opened)
—
External brake, frequency threshold opening
0.00–P6.4 Hz
Condition: RUN (Start enable)
If the frequency set here is exceeded, the brake is actuated
(P5._is opened)
—
External brake, frequency threshold closing
0.00–P6.4 Hz
If the frequency goes below the value set here, the brake is
actuated (P5._ is closed)
—
External brake, frequency threshold REV closing
0.00–P6.4 Hz
—
—
External brake, current limit, opening
0.00–P7.2A
Condition: RUN (Start enable)
On reaching the current value set here, the brake is actuated
(P5._ is opened)
M-Max Series Adjustable Frequency Drive MN04020003E—October 2013 www.eaton.com
Mechanical Brake
f
(Hz)
P12.9
P12.8
RUN
(FWD/REV)
R01, R02, DO
(P5... = 26)
1
Item
Number
Description
1
Brake, released
2
Brake activates and brakes the drive mechanically
Parameters
STOP
P6.8 = 1
t
2
Factory Setting
(P1.3)
0.2
1.50
1.50
1.50
0.00
117