Engineering
Motor and Circuit Type
The motor's stator winding can be connected in a star or
delta configuration, in accordance with the rated operational
data on the nameplate.

Example of a Motor Ratings Plate

230
/400
V
S1
0.75
kW
cos
RPM
1430

Star and Delta Circuit Types

U1 V1 W1
U1 V1 W1
W2 U2 V2
W2 U2 V2
The three-phase motor with the rating plate based on the
figure shown above, can be run in a star or delta connection.
The operational characteristic curve is determined by the
ratio of motor voltage and motor frequency, in this case.
87-Hz Characteristic Curve
In the delta circuit with 400V and 87 Hz, the motor shown in
the figure above was released with three times-fold output
(~1.3 kW).
Assignment of Frequency Inverters to Example Motor Circuit (See Figure Above)
Frequency Inverters
Rated operational current
Input voltage
Motor circuit

V/Hz-characteristic curve

Motor current
Motor voltage
Motor speed
Motor frequency
Notes
Star connection: 400V, 50 Hz.
Delta connection: 230V, 50 Hz.
Delta connection: 400V, 87 Hz.
Note the permitted limit values of the motor.
24
M-Max Series Adjustable Frequency Drive MN04020003E—October 2013 www.eaton.com
3.5/2
A
0.79
50 Hz
MMX12AA3D7_
3.7A
1 AC 230V
Delta
3.5A
3 AC 0–230V
–1
1430 min
50 Hz
Because of the higher thermal loading, using only the next
higher motor output according to the list (1.1 kW) is
recommended. The motor (in this example) therefore still has
1.47-fold higher output compared with the listed output
(0.75 kW).
With the 87-Hz characteristic curve, the motor also works in
the range from 50 to 87 Hz with an unattenuated field. The
pull-out torque remains at the same level as in input
operation with 50 Hz.
The heat class of the motor must be at least F in 87-Hz
operation.
V/Hz-Characteristic Curve
U
(V)
2
400
230
0
50
The following table shows the allocation of possible
frequency inverters depending on the input voltage and the
type of circuit.
MMX32AA3D7_
MMX34AA2D4_
3.7A
2.4A
1 AC 230V
3 AC 400V
Delta
Star
3.5A
2.0A
3 AC 0–230V
3 AC 0–400V
–1
1430 min
1430 min
50 Hz
50 Hz
87
f (Hz)
f
max
MMX34AA4D3_
4.3A
3 AC 400V
Delta
3.5A
3 AC 0–230V
–1
–1
2474 min
87 Hz