Digital Output

Access
PNU
ID
RUN
P5.1
313
P5.2
314
P5.3
312
P5.4
315
P5.5
316
P5.6
346
P5.7
347
P5.8
1457
ro/rw
Designation
rw
RO1 Signal
(Relay 1 Output)
rw
RO2 signal
(relay output 2)
rw
DO Signal
(Digital Output)
rw
Frequency monitoring 1
rw
Frequency monitoring 1
reference value
rw
Frequency monitoring 2
rw
Frequency monitoring 2
reference value
rw
Current monitoring
M-Max Series Adjustable Frequency Drive MN04020003E—October 2013 www.eaton.com
Value Range
0 = Deactivated
1 = READY
2 = RUN
3 = FAULT
4 = Error message (inverted)
5 = ALARM
6 = REV
7 = Output frequency
8 = Motor controller active
9 = Zero frequency
10 = Frequency monitoring 1
11 = Frequency monitoring 2
12 = PID monitoring
13 = Overtemperature signal
14 = Overcurrent control active
15 = Overvoltage control active
16 = PLC Sequence control active
17 = PLC sequence control, single step
completed
18 = PLC sequence control, program cycle
completed
19 = PLC sequence control, pause
20 = Counter, value 1 reached
21 = Counter, value 2 reached
22 = RUN message active
23 = Analog min reference error
24 = LOG function fulfilled
25 = PID controller, actual value
monitoring
26 = External brake actuated
27 = Current monitoring
28 = Fieldbus, remote output
Like P5.1
Like P5.1
0 = Deactivated
1 = 0.00–P5.5 Hz
2 = P5.5–P6.4 Hz
0.00–P6.4 Hz
0 = Deactivated
1 = 0.00–P5.7 Hz
2 = P5.7–P6.4 Hz
0.00–P6.4 Hz
0.00–P7.2A
Appendix A
FS
User
Page
(P1.3)
Setting
78
2
79
3
79
1
79
0
80
0.00
80
0
80
0.00
81
0.00