Parameters
Drives Control, continued
Access
PNU
ID
RUN
P6.15
184
P6.16
1474
P6.17
1427
X
P6.18
1428
X
P6.19
502
P6.20
503
P6.21
526
X
P6.22
1334
X
P6.23
1429
X
86
M-Max Series Adjustable Frequency Drive MN04020003E—October 2013 www.eaton.com
Value/Range
Description
Keypad frequency reference (REF)
–P6.4–P6.4 Hz
The setpoint value (REF) defined here can be activated at
parameter P6.2 and via the keypad (LOC/REM)
In KEYPAD mode, the value can be changed with the arrow
buttons. The changes are written back automatically to this
parameter (P6.15)
Stop button active
In the default settings, the STOP button of the keypad is
active in all operating modes
The Stop function can be set at parameter P6.8
0
No (deactivated)
Stop executed only via control signal terminals (I/O) or
fieldbus (BUS)
Switching the LOC/REM button to KEYPAD removes the
block on the STOP button function set here
Note: This does not deactivate the Reset function (FS
loading with 5s actuation of the STOP button)
1
Yes (activated)
Secondary remote control source
Assignment of the control levels as at P6.1
Control level 2 is activated via parameter P3.25
Secondary remote speed reference
Assignment of setpoint sources as at P6.2
Setpoint source 2 is activated via parameter P3.26
Secondary acceleration time (acc2)
0.1–3000s
See Note 1 of parameter P6.5
The activation is executed via parameter P3.15
Secondary deceleration time (dec2)
0.1–3000s
See Note 1 of parameter P6.6
The activation is executed via parameter P3.15
Acceleration transition frequency (acc1–acc2)
0.00–P6.4 Hz
0.00 Hz = deactivated
If the output frequency set here is exceeded, the
acceleration time is switched automatically from acc1 (P6.5)
to acc2 (P6.19)
Deceleration transition frequency (dec1–dec2)
0.00–P6.4 Hz
0.00 Hz = deactivated
If the output frequency set here is exceeded, the
deceleration time is switched automatically from dec1 (P6.6)
to dec2 (P6.20)
REV blocked
The rotating field reversal of the output frequency is blocked
0
Deactivated
1
Activated
Factory Setting
(P1.3)
0.00
1
3
2
10.0
10.0
0.00
0.00
0