The run times in the individual program steps must be
greater than the transition times for the subsequent
frequency value. Example as per figure on Page 104
(Example A):
Acceleration time P6.5 = 3.0s
Maximum frequency P6.4 = 60 Hz
FF1: P10.2 = 20 Hz
FF2: P10.3 = 40 Hz
Fixed Frequency Setpoint Value
Access
PNU
ID
RUN
P10.11
1438
P10.12
1439
P10.13
1440
P10.14
1441
P10.15
1442
P10.16
1443
P10.17
1444
P10.18
1445
Value/Range
Description
—
Set time for FF0
0–1000s
0s = Fixed frequency FF0 deactivated
(sequence control P10.9)
—
Set time for FF1
0–1000s
0s = Fixed frequency FF1 deactivated
(sequence control P10.9)
—
Set time for FF2
0–1000s
0s = Fixed frequency FF2 deactivated
(sequence control P10.9)
—
Set time for FF3
0–1000s
0s = Fixed frequency FF3 deactivated
(sequence control P10.9)
—
Set time for FF4
0–1000s
0s = Fixed frequency FF4 deactivated
(sequence control P10.9)
—
Set time for FF5
0–1000s
0 s = Fixed frequency FF5 deactivated
(sequence control P10.9)
—
Set time for FF6
0–1000s
0s = Fixed frequency FF6 deactivated
(sequence control P10.9)
—
Set time for FF7
0–1000s
0s = Fixed frequency FF7 deactivated
(sequence control P10.9)
M-Max Series Adjustable Frequency Drive MN04020003E—October 2013 www.eaton.com
FF x P6.5
t FF
P6.4
(P10.3–P10.4) x P6.5
P10.13
P6.4
The transition time from FF1 to FF2 is one second.
Parameter P10.13 should therefore be set to a value greater
than one second.
Parameters
(40 Hz–20 Hz) x 3s
1s
60 Hz
Factory Setting
(P1.3)
0
0
0
0
0
0
0
0
103